Data Normalization
Template: TStat_HeatPump_Trane
This section lists special data normalizations for points in this template.
Tracer SC Point name: Occupancy Status
BACnet point name, type, and instance: Effective
Occupancy (MV 34)
Tracer SC state and text Heat pump state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Occupied Bypass 1 - Occupied
4 - Occupied Standby 1 - Occupied
5 - Auto 1 - Occupied
Tracer SC Point name: Occupancy Request
BACnet point name, type and instance: Occupancy Command (MV 12)
Tracer SC Point name: Heat Cool Mode Request
BACnet point name, type and instance: System Mode (MV 13)
Table 32. Tracer SC writing to the heat pump (Occupancy Status)
Table 33. Reading from heat pump to Tracer SC (Occupancy Status)
Heat pump state and text Tracer SC state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Temporary Occupied 1 - Occupied
Table 34. Tracer SC writing to the heat pump (Occupancy Request)
Tracer SC state and text Heat pump state and text
1 - Occupied 2 - Occupied
2 - Unoccupied 3 - Unoccupied
3 - Occupied Bypass 2 - Occupied
4 - Occupied Standby 2 - Occupied
5 - Auto 1 - Local Occupancy
Table 35. Reading from heat pump to Tracer SC (Occupancy Request)
Heat pump state and text Tracer SC state and text
1 - Local Occupancy 5 - Auto
2 - Occupied 1 - Occupied
3 - Unoccupied 2 - Unoccupied