Toshiba RAV-SP300AT2-UL Air Conditioner User Manual


 
– 74 –
10. SETUP AT LOCAL SITE AND OTHERS
10-1. Outdoor Unit
10-1-1. Various Setting on Outdoor Unit (Power save, Cooling-only, etc.)
The following settings are available by DIP switch setup and jumper line setup.
<RAV-SP180AT2-UL>
Power saving setting
Cooling only setting
SW802
321
ON
Function
Power save
setup
Cooling-only
setup
Set position Control contents
When using the power saving function, turn on switches.
The control to lower the compressor frequency (approx. -10%) is
performed by indoor heat exchanger temp. in heating operation.
When using the outdoor unit as a cooling-only machine, turn on
switches. (“OF” of DN cord on the remote controller also can be
used for changing the machine to the cooling-only model.)
<RAV-SP240, SP300, SP360, SP420AT2-UL>
Function
High static
pressure
setup
Power save
setup
Snow-proof
fan control
Defrost
time change
Max.
frequency
change
Cooling-only
setup
Set position
J805, J806
J807
J808
Control contents
Turn the switch to ON when mounting a duct to the discharge port
of the outdoor unit.
Add 3 taps to the upper limit value of the outdoor fan tap.
The operation is performed with
(Max: Upper fan: 890 rpm / Lower fan: 910 rpm (WF)).
In this case, the upper limit value of static pressure for duct is 5Pa
or less on 77°F (25°C) degrees and please use straight duct.
In this case, the outdoor noise level may increase.
Turn the switch to ON when using the power save function.
The control to lower the compressor frequency (Approx. –10%) is
performed by indoor heat exchanger temp. in heating operation.
When snow enters from clearance of the fan guard or heat
exchanger into blast path and it is accumulated, the control to
prevent generation of motor lock is validated.
When outside temp. is below 32°F (0°C) though the compressor
stops, the outdoor fan operates with W5.
The defrost interval is cut to shorten it than the standard status.
For contents of control and cutting method, refer to
10. Defrost control (See to Page 43).
When it is needed to lower the maximum value of the compressor
frequency, cut the jumper line. Max. frequency at cooling/heating is
lowered.
In this case the Max. capacity decreases.
Max. frequency of compressor
When using the air conditioner as a cooling-only conditioner, cut
the jumper line. (An air conditioner can be changed to cooling-only
conditioner by “0F” of DN code on the remote controller.)
4321
ON
High static pressure setup
Power save setup
Snow-proof fan control
SW802
all are OFF at shipment.
RAV-
Model
Standard status
When J807 is cut
SP240
COOL HEAT
72.0 99.6
72.0 79.2
SP300
COOL HEAT
53.4 71.4
53.4 64.2
SP360, SP420
COOL HEAT
64.2 90.6
64.2 72.0