Toshiba RAV-SP300AT2-UL Air Conditioner User Manual


 
– 50 –
8-2-3. Check Code List (Outdoor)
¡
: Go on,
¥
: Flash,
l
: Go off
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
²
When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.
Remote
controller
indication
F04
F06
F08
F07
F12
F13
F15
F31
H01
H02
H03
H04
L10
L29
P03
P04
P05
P07
P15
P20
P22
P26
P29
E01
E02
E03
E04
E08
E09
E10
E18
L03
L07
L08
L09
L30
P19
Sensor lamp part
Block indication
Operation
Timer Ready Flash
¥¥¡
ALT
¥¥¡
ALT
¥¥¡
ALT
¥¥¡
ALT
¥¥¡
ALT
¥¥¡
ALT
¥¥¡
ALT
¥¥¡
SIM
l
¥
l
l
¥
l
l
¥
l
l
¥
l
¥¡¥
SIM
¥¡¥
SIM
¥
l
¥
ALT
¥
l
¥
ALT
¥
l
¥
ALT
¥
l
¥
ALT
¥
l
¥
ALT
¥
l
¥
ALT
¥
l
¥
ALT
¥
l
¥
ALT
¥
l
¥
ALT
¥
ll
¥
ll
¥
ll
ll
¥
¥
ll
¥
ll
¥
ll
¥
ll
¥
l
¥
SIM
¥
l
¥
SIM
¥
l
¥
SIM
¥
l
¥
SIM
¥¡¥
SIM
¥
l
¥
ALT
Representative defective position
Outdoor unit Discharge temp. sensor (TD) error
Outdoor unit Temp. sensor (TE, TS, TL) error
Outdoor unit Outside temp. sensor (TO) error
Outdoor unit Temp. sensor (TL) error
Outdoor unit Temp. sensor (TS) error
Outdoor unit Temp. sensor (TH) error
Outdoor unit Misconnection of temp. sensor (TE, TS)
Outdoor unit EEPROM error
Outdoor unit Compressor break down
Outdoor unit Compressor lock
Outdoor unit Current detection circuit error
Outdoor unit Case thermostat operation
Outdoor unit Setting error of service P.C. board type
Outdoor unit Other outdoor unit error
Outdoor unit Discharge temp. error
Outdoor unit
High pressure system error, Power supply voltage error
Power supply error
Outdoor unit Heat sink overheat
Gas leak detection
Outdoor unit High pressure system error
Outdoor unit Outdoor fan error
Outdoor unit Inverter Idc operation
Outdoor unit Position detection error
No remote controller master unit
Remote controller communication error
Remote controller send error
Regular communication error between indoor and
remote controller
Indoor/Outdoor serial error
Duplicated indoor addresses
²
Duplicated main remote controllers
Communication error between CPU
Regular communication error between header and
follower indoor units
Duplicated indoor header units
²
There is group cable in individual indoor unit.
²
Unset indoor group address
²
Unset indoor capacity
Outside error input to indoor unit (Interlock)
4-way valve inverse error
Detection
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Remote
controller
Remote
controller
Indoor
Indoor
Indoor
Remote
controller
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Explanation of error contents
Open/Short of discharge temp. sensor was detected.
Open/Short of heat exchanger temp. sensor was detected.
Miswiring between TE sensor and TS sensor
Open/Short of outside temp. sensor was detected.
Open/Short of heat exchanger temp. sensor was detected.
Open/Short of suction temp. sensor was detected.
Open/Short of heat sink temp. sensor (Board installed) was detected.
Misconnection of outdoor heat exchanger temp. sensor and suction temp. sensor was detected.
Outdoor P.C. board part (EEPROM) error was detected.
When reached min-Hz by current release control, short-circuited current (Idc) after
DC excitation was detected.
Compressor lock was detected.
Current detection circuit error
Case thermostat operation was detected.
When outdoor service P.C. board was used, model type select jumper setting was inappropriate.
1) Defective parts on outdoor P.C. board (MCU communication, EEPROM, TH sensor error)
2) When outdoor service P.C. board was used, model type selection was inappropriate.
3) Other error (Heat sink abnormal overheat, gas leak, 4-way valve inverse error) was detected.
Error was detected by discharge temp. release control.
When case thermostat worked or High-pressure SW worked error was detected
by high release control from indoor/outdoor heat exchanger temp. sensor. Power supply voltage error
Power supply voltage error
Abnormal overheat was detected by outdoor heat sink temp. sensor.
Abnormal overheat of discharge temp. or suction temp. was detected.
Error was detected by high release control from indoor/outdoor heat exchanger temp. sensor.
Error (Over-current, lock, etc.) was detected on outdoor fan drive circuit.
Short-circuited protective operation of compressor drive circuit element (G-Tr /IGBT) worked.
Position detection error of compressor motor was detected.
Signal was not received from indoor unit.
Main remote controller was not set. (including 2 remote controllers)
Signal cannot be sent to indoor unit.
No communication from remote controller and network adapter
Serial communication error between indoor and outdoor
Same address as yours was detected.
In 2-remote controller control, both were set as master.
(Indoor header unit stops warning and follower unit continues operation.)
MCU communication error between main motor and micro computer
Regular communication was impossible between master and follower indoor units.
There are multiple header units in a group.
When even one group connection indoor unit exists in individual indoor unit
Indoor address group was unset.
Capacity of indoor unit was unset.
Abnormal stop by CN80 outside error input
In heating operation, error was detected by temp. down of indoor heat exchanger or temp. up ofTE, TS.
Automatic Operation
reset
continuation
××
××
¡¡
××
××
××
××
××
××
××
××
××
××
××
××
××
××
××
××
××
××
××
××
——
——
¡ ×
¡ ×
¡
××
¡
¡ ×
××
××
××
××
××
¡ ×