Toshiba CONCEALED DUCK TYPE Air Conditioner User Manual


 
– 90 –
No.
4
Part name
Ceiling panel
Procedure
1. Detachment
1) Perform works of procedure
1
-1-,
2
-1,
and
3
-1.
2) Remove the flap connector (CN33, White, 5P)
connected to the control P.C. board and then
take off the lead wire from the clamp.
NOTE)
Remove the connectors after unlocking the lock of
the housing.
3) Take off screws (M5, 4 pcs.) fixing the ceiling
panel.
4) Push the temporary bracket to inner side to
remove the ceiling panel.
2. Attachment
1) Hook the panel to the temporary bracket of
the drain pan of the main body.
NOTE)
The panel has directionality.
Therefore mount the panel according to the temporary
bracket and the bracket mounting position.
2) Tighten the fixing screws. (M5, 4 pcs.)
3) Connect flap connector of the
ceiling panel to the connector
(CN33, White, 5P) of the
control P.C. board.
Hanging
section of tentative
hook of ceiling panel
Temporary
bracket
Push to remove
Drain piping
corner
Ceiling panel
Hanging section
of temporary bracket
Washer
based screw
Cable clamp
CN33
Temporary
bracket
Remarks