Toshiba CONCEALED DUCK TYPE Air Conditioner User Manual


 
– 73 –
DN
60
8b
42
C2
CC
CD
D0
D1
D3
D4
Item
Timer set
(Wired remote controller)
Correction of high heat feeling
Self clean time
Power saving
(Current demand × % to outdoor unit)
Forced stop setting for self clean
Self clean stop function when [START/
STOP] operation was prohibited
Existence of Power save operation
Existence of 8°C heating operation
function
Revolution count of self clean
Display/ No display of [SELF CLEANING]
during self clean operation
Description
0000 : Available (Operable)
0001 : Unavailable (Operation prohibited)
0000 : None 0001 : Correction
0000: None
0001: 0.5h to 0.012: 6.0h
The case that compressor-ON time is 10 to 60 minutes is
set up. When ON time is over 60 minutes, the operating
time becomes two times of it.
0050: 50% to 0100: 100%
0000: None 0001: Set
When stopping the air conditioner (including “Fire alarm”
of the control system, etc.) while [START/STOP] operation
is prohibited (Central 1, 2) from the central controller side,
0000: Valid (No self cleaning)
0001: Invalid (Self cleaning)
0000: Invalid (Unavailable)
0001: Valid (Available)
0000: Invalid (Unavailable)}
0001: Valid (Available)
0000: Invalid (Self cleaning is not performed.)
0001: Valid (Self cleaning is performed at 210 rpm.)
0000: Displayed, 0001: Not displayed
At shipment
0000 : Available
0000 : None
0002: 1 hour
0075: 75%
0000: None
0000: Valid
0001: Valid (Available)
0000: Invalid
(Unavailable)
0001: Valid
(210rpm/operation)
0000: Displayed