7/50D Plus or 7/50D Controller Chapter 4: Operation 67
1. Touch Source Pump.
The keypad pops up.
2. Enter the number of the failed pump. Use ← to erase any mistakes. Use ↵ to enter the
value.
The number appears under Source Pump.
3. Touch Standby Pump.
The keypad pops up.
4. Enter the number of the standby pump. Use ← to erase any mistakes. Use ↵ to enter
the value.
The number appears under Standby Pump, and a button labeled Transfer to
Standby Pump appears on the screen:
Note: When you enter the second pump number, the controller checks to
make sure that both pumps are offline and that the standby pump has
no stations assigned to it. If these conditions are not all met, error
messages appear on the screen instead of a Transfer to Standby
Pump button. If you get an error message, first check to make sure that
you have entered the correct numbers and reenter if necessary.
If the error message tells you to disable the source pump and/or the standby pump, touch
Return at this screen, then Pumps at the Pump n Setup screen. Take the pumps offline and
then return to the Transfer to Standby Pump screen.
If the error message tells you that the standby pump has stations assigned, you must either use
a different standby pump or you must remove the pump assignment for all stations assigned
to the standby pump. To remove the assignments, touch Return at this screen, then
Stations at the Pump n Setup screen.