Parameters
WE Parameter level / Range of values
Day set point 20 °C PA1, 2, 3 / 10 to 90 °C
Night set point 17 °C PA1, 2, 3 / 10 to 90 °C
Sustained temperature 10 °C PA1, 2, 3 / 10 to 90 °C
5.10 Flash adaptation
Direct reactions to deviations in room temperature can be achieved using the function block set
-
ting: Co1, 2, 3 -> Fb08 = ON.
Flash adaptation counteracts room temperature deviations by increasing or decreasing the flow
temperature by up to 30 °C. The shift is displayed under
Level
in PA1, 2, 3 parameter levels; it
cannot be altered. The set point correction over remote room panel is not possible.
Note!
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated when the cooling load has been eliminated!
Functions
WE Configuration
Room sensor RF1, 2, 3 OFF Co1, 2, 3 -> Fb00 = ON
Flash adaptation OFF Co1, 2, 3 -> Fb08 = ON
5.11 Adaptation
The controller is capable of automatically adapting the heating characteristic to the building
characteristics, provided a gradient characteristic has been set (Co1, 2, 3 -> Fb10 = OFF). The
reference room, where the room sensor is located, represents the entire building and is moni
-
tored to ensure that the
Day set point
is maintained. When the mean measured room tempera
-
ture in rated operation deviates from the adjusted set point, the heating characteristic is modi
-
fied accordingly for the following time-of-use. The corrected value is displayed in PA1, 2, 3 pa
-
rameter levels under
Gradient, flow
.
Functions
WE Configuration
Room sensor RF1, 2, 3 OFF Co1, 2, 3 -> Fb00 = ON
Outdoor sensor AF1, 2, 3 Co1, 2, 3 -> Fb02 = ON
Adaptation OFF Co1, 2, 3 -> Fb07 = ON
4-point characteristic OFF Co1, 2, 3 -> Fb10 = OFF
48 EB 5179 EN
Functions of the DHW circuit