Co6: Sensor initialization
Fb Function WE Anl
Comments
Function block parameters / Range of values (default setting)
00 Sensor selection
general
ON All Co6 -> Fb00 = ON: Pt 100; Pt 1000
Co6 -> Fb00 = OFF: Pt 100; PTC
01
to
17
Sensor input 1
to
sensor input 17
OFF All
Any sensor inputs that are different from the settings for
function block Fb00
Co6 -> Fb01 to Fb17 = ON: select:
Outdoor temperature input:
0/4 to 20 mA, 0 to 10 V = –40 to 50 °C
Other temperature inputs:
0/4 to 20 mA, 0 to 10 V = 0 to 160 °C
Ni200, Ni1000, PTC, NTC, Pt1000, Pt100, 0/4-20, 0-10
23 Sensor calibration OFF All
Fb Function block, WE Default setting
Co7: LON communication
Fb Function WE Anl
Comments
Function block parameters / Range of values (default setting)
00 LON active OFF All Co7 -> Fb00 = ON: LON interface active
01 Controller as
master controller
OFF All Co7 -> Fb01 = ON: Controller is defined as primary controller
(processes the external demand as master controller)
Co7 -> Fb01 = OFF: Controller is defined as secondary
controller
02 Controller time OFF All Co7 -> Fb02 = ON: Controller time = LON system time
03 Outdoor
temperature 1
OFF All Co7 -> Fb03 = ON: LON outdoor temperature 1
Select: Terminal number of outdoor sensor
04 Outdoor
temperature 2
OFF All Co7 -> Fb04 = ON: LON outdoor temperature 2
Select: Terminal number of outdoor sensor
05 Report operational
faults of other LON
participants
OFF All Co7 -> Fb05 = ON: Report fault alarms of other LON
participants
Fb Function block, WE Default setting
104 EB 5179 EN
Appendix