1.6.3 Entering vacation periods
During vacation periods, the controller constantly remains in the reduced operating mode. The
system is monitored for frost. A maximum of 10 vacation periods can be entered.
Parameters
WE Level / Range of values
Vacation period for heating circuit 1 – PA1 / 01.01 to 31.12
Vacation period for heating circuit 2 – PA2 / 01.01 to 31.12
Vacation period for heating circuit 3 – PA3 / 01.01 to 31.12
Note!
The programmed public holidays and vacations of any heating circuit (HK1, HK2 or HK3) ap
-
ply with the setting Co4 -> Fb12 = ON , select 1, 2 or 3 also for the DHW heating.
Proceed as follows: Switch to configuration and parameter level.
Display:
PA1
Select parameter level.
Open parameter level.
Select datapoint for vacation periods.
Display shows:
Open datapoint for vacation periods.
Display shows
: START
If applicable, select
– – – –
.
Activate editing mode for vacation periods.
blinks.
Set start date of vacation period.
Confirm start date of the vacation period.
Display shows:
STOP
Set end of vacation period.
Confirm end of the vacation period.
To enter additional vacation periods, re-select
––––
(between 31.12 and 01.01) and repeat
the steps in the fields highlighted in gray.
Exit the parameter level.
18 EB 5179 EN
Operation
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24