Samson 5179 Thermostat User Manual


 
Function
WE Configuration
Differential temperature control using variable
weighting factors
OFF
0.5
200 s
20 °C
90 %
30 %
Co1, 2, 3 -> Fb18 = ON
Proportional gain factor K
P
/0.1 to 999
Reset time T
N
/ 1 to 999 s
Intended temp. difference / 0 to 40 °C
Analog value max. / 0 to 100 %
Analog value min. / 0 to 100 %
Parameters
WE Parameter level / Range of values
Max. return flow temperature* 65 °C PA1, 2, 3 / 20 to 90 °C
Min. return flow temperature* 20 °C PA1, 2, 3 / 20 to 90 °C
* Can only be selected when Co5 -> Fb01 = ON,
select:
steig
Note!
Only one function can be assigned to an analog output (e.g. flow temperature control, passing
on the outdoor temperature or differential temperature control).
5.5 Deactivation depending on outdoor temperature
5.5.1 OT deactivation value in rated operation
If the outdoor temperature exceeds the limit
OT deactivation value in rated operation
, the affected
heating circuit is put out of service immediately. The valve is closed and the pump is switched off
aftert=2x
Valve transit time
. When the outdoor temperature falls below this value (less 0.5 °C
hysteresis), heating operation is restarted immediately.
With the default settings, this means that, during the warm season, the system is switched off at an
outdoor temperature of 22 °C.
Parameter
WE Parameter level / Range of values
OT deactivation value
in rated operation
22 °C PA1, 2, 3 / 0 to 90 °C
5.5.2 OT deactivation value in reduced operation
If the outdoor temperature in reduced operation exceeds the limit
OT deactivation value in re
-
duced operation
, the affected heating circuit is put out of service immediately. The valve is closed
and the pump is switched off aftert=2x
Valve transit time
.
EB 5179 EN 43
Functions of the heating circuit