Samson 5100 Thermostat User Manual


 
Settings for flow rate limitation
Functions
WE Configuration
Limitation of heat meter (WMZ) OFF Co5 -> Fb08 = OFF
Pulse input for flow rate or capacity limitation OFF
10
Co5 -> Fb09 = ON,
select:
U
CONST: Limitation constant
4-Pt: Limitation acc. to
4-point characteristic
Pulse weighting / 0.1 to 10
Parameters
WE Parameter level / Range of values
Maximum flow rate of the entire system 9 m
3
/h PA5 / 0.01 to 99.9 m
3
/h
Maximum flow rate of the DHW heating 9 m
3
/h PA5 / 0.01 to 99.9 m
3
/h
Proportional-action coefficient for the limitation 1.0 PA5 / 0.1 to 10
Select
CONST
additionally for:
Maximum flow rate of the heating 9 m
3
/h PA5 / 0.01 to 99.9 m
3
/h
Select
4-Pt
additionally for:
Outdoor temperature Point 1
Point 2
Point 3
Point 4
–15 °C
– 5 °C
5 °C
15 °C
PA5 /–30 to 90 °C
Maximum flow rate limitation, points 1 to 4 9 m
3
/h PA5 / 0.01 to 99.9 m
3
/h
A second pulse counter can be connected at terminal 29. The pulses entered are stored in the
holding registers 40031 (low byte) and 40032 (high byte). The associated duration on the
holding registers 40035 (low byte) and 40036 (high byte). First, the low byte counts upwards
(0 to 65535). If several pulses arrive, the counting value is formed by multiplying the low byte
with the high byte (32-bit value).
7.12 Locking manual level
To protect the heating system, this function can be used to lock manual level. When this function
has been activated, automatic mode is started when the rotary switch is set to +, or 0.
Function
WE Configuration
Locking manual levels OFF Co5 -> Fb10 = ON
66 EB 5179 EN
System-wide functions