Parameters
PA1 PA2 PA3
Range of values
Times-of-use
Monday Start – Stop (1) 00:00 to 24:00 h
Monday Start – Stop (2) 00:00 to 24:00 h
Tuesday Start – Stop (1) 00:00 to 24:00 h
Tuesday Start – Stop (2) 00:00 to 24:00 h
Wednesday Start – Stop (1) 00:00 to 24:00 h
Wednesday Start – Stop (2) 00:00 to 24:00 h
Thursday Start – Stop (1) 00:00 to 24:00 h
Thursday Start – Stop (2) 00:00 to 24:00 h
Friday Start – Stop (1) 00:00 to 24:00 h
Friday Start – Stop (2) 00:00 to 24:00 h
Saturday Start – Stop (1) 00:00 to 24:00 h
Saturday Start – Stop (2) 00:00 to 24:00 h
Sunday Start – Stop (1) 00:00 to 24:00 h
Sunday Start – Stop (2) 00:00 to 24:00 h
Function block parameters Co1, Co2, Co3
Limitation factor (Fb01 = ON) 0 to 25.5
Advance heating time (Fb05 = ON) 0 to 360 min
Start summer mode (Fb11 = ON) 01.01 to 31.12
Stop summer mode (Fb11 = ON) 01.01 to 31.12
Outdoor temp. limit in summer mode
(Fb11 = ON)
0 to 30 °C
K
P
(proportional gain) (Fb14/15 = ON) 0.1 to 50
T
N
(reset time) (Fb14/15 = ON) 1 to 999 s
T
V
(derivative-action time) (Fb14 = ON) 0 to 999 s
T
Y
(valve transit time) (Fb15 = ON) 15 to 240 s
UP lag time (Fb15 = ON/OFF) 120 to 1200 s
Hysteresis (Fb15 = OFF) 1 to 30 °C
Min. activation time (Fb15 = OFF) 0 to 600 s
Min. deactivation time (Fb15 = OFF) 0 to 600 s
Proportional gain (K
P
) (Fb18 = ON) 0.1 to 999
Reset time (T
N
) (Fb18 = ON) 1 to 999 s
132 EB 5179 EN
Appendix