Samson 5100 Thermostat User Manual


 
Parameters PA5 Range of values
Outdoor temperature, point 3 –30 to 90 °C
Outdoor temperature, point 4 –30 to 90 °C
Return flow temperature, point 1 20 to 90 °C
Return flow temperature, point 2 20 to 90 °C
Return flow temperature, point 3 20 to 90 °C
Return flow temperature, point 4 20 to 90 °C
Max. limit of flow rate, point 1 0 to 99.9 m
3
/h
Max. limit of flow rate, point 2 0 to 99.9 m
3
/h
Max. limit of flow rate, point 3 0 to 99.9 m
3
/h
Max. limit of flow rate, point 4 0 to 99.9 m
3
/h
Max. limit of capacity, point 1 0 to 5999 kW
Max. limit of capacity, point 2 0 to 5999 kW
Max. limit of capacity, point 3 0 to 5999 kW
Max. limit of capacity, point 4 0 to 5999 kW
V-offset of the entire system –300 to 300 m
3
/h
P-offset of the entire system –3000 to 3000 kW
Function block parameters Co5
Delay (Fb04 = ON) 1 to 6 °C
Max. system deviation (Fb07 = ON) 2 to 10 °C
Pulse weighting (Fb09 = ON) 0.1 to 10
Boost (Fb13 = ON) 0 to 30 °C
T
Y
(valve transit time) (Fb14 = ON) 15 to 240 s
K
P
(proportional gain) (Fb14/19 = ON) 0.1 to 50
T
N
(reset time) (Fb14/19 = ON) 1 to 999 s
Hysteresis (Fb14 = OFF) 1 to 30 °C
Min. activation time (Fb14 = OFF) 0 to 600 s
Min. deactivation time (Fb14 = OFF) 0 to 600 s
T
V
(derivative-action time) (Fb19 = ON) 0 to 999 s