Regency P40-LP Indoor Fireplace User Manual


 
Regency
®
P40 Direct Vent Gas Fireplace 39
MAINTENANCE
VALVE REPLACEMENT
1) Shut off the main gas supply and unplug
the power to the ECS system.
2) Remove the main gas line pipe from the
gas valve.
3) Remove logs and brick panels if installed.
4) Remove the fender by undoing the 2 screws,
one on the left and right side.
5) Remove the front air box by undoing the 3
screws.
Fender
6) Remove the front burner by removing the 2
screws and swing the burner to the left and
slide out.
Front Air Box
7) Carefully remove the base brick panel.
8) Remove the 2 screws on the back burner.
9) Slide burner to the right and lift out.
10) Remove back air box by removing 2 screws,
one on the left and one on the right side and
pull out.
Back Burner
14) Remove all 22 valve tray screws and care-
fully lift out the valve tray.
Back
Burner
MAINTENANCE
11) Unplug the 3 black wires at the DC
Sparker.
12) Unplug the 5 wires at the valve (2 grey, 2
red and 1 black.
13) Reach in and grab the black and red wires
leading to the solenoid valve and disconnect
them.
Solenoid Valve