INSTALLATION
H
H1
V
Horizontal Venting with Two (2) 90
o
Elbows
Horizontal Venting with Three (3) 90
o
Elbows
One 90
o
elbow = Two 45
o
elbows.
One 90
o
elbow = Two 45
o
elbows.
Option V H + H1
A) 2' Min. 2' Max.
B) 3' Min. 5' Max.
C) 4' Min. 6' Max.
D) 5' Min. 7' Max.
E) 6' Min. 8' Max.
With these options,
maximum total pipe length
is 30 feet with minimum
of 6 feet total vertical
and maximum 8 feet total
horizontal.
Option V H V + V1 H + H1
A) 0' Min. 1' Max. 1' Min. 1' Max.
B) 1' Min. 2' Max. 3' Min. 3' Max.
C) 2' Min. 2' Max. 5' Min. 4' Max.
D) 3' Min. 2' Max. 7' Min. 5' Max.
E) 4' Min. 3 Max. 9' Min. 6' Max.
F) 5' Min. 4' Max. 10' Min. 7' Max.
G) 6' Min. 5' Max. 11' Min. 8' Max.
H) 7' Min. 6' Max. 12' Min. 9' Max.
With these options,
max. total pipe length
is 30 feet with min. of
12 feet total vertical
and max. 9 feet total
horizontal.
Please note min. 1
foot between 90
o
elbows is required.
VENT RESTRICTOR SETTING:
When total vertical exceeds total horizontal by 2x the vent
restrictor setting is set to 1.
Please note minimum 1 foot between 90
o
elbows is
required.
INSTALLATION
VENT RESTRICTOR SETTING:
When total vertical exceeds total horizontal by 3x the vent restrictor
setting is set to 1.