Regency L676-1 Indoor Fireplace User Manual


 
Regency
®
L676-1 Direct Vent Gas Fireplace 9
INSTALLATION
INSTALLATION
Caution Requirements
The top, back and sides of the replace are de ned by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials
are not adhered to. It is of greatest importance that this
replace and vent system be installed only in
accordance with these instructions.
IMPORTANT
If converting this unit to LP, it is highly recommened
the conversion be done BEFORE the unit is slid into
position for ease of conversion. See "Conversion
from NG to LP" section for instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this replace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back 0" (0mm)
Side 0" (0mm)
Floor 0" (0mm)
Minimum Clearance from Top of Front Facing:
Mantel min. 16-1/2" (419mm)
Ceiling 52" (813mm) from top of front facing
Side Wall to Unit:
14-3/4"* (375mm)
Horizontal Vent Clearances to Combustibles:
Top 3" (76mm)
Side 2" (51mm)
Bottom 2" (51 mm)
Vertical Vent Clearances to Combustibles:
All Sides 2" (51mm)
Alcove Clearances:
Min. Depth 36" (914mm)
Min. Width* 84" (2134mm)
Min. Height 84" (2032mm)
* Alcove side wall must have a minimum of 14-3/4" (375mm) clearance on one side.
IMPORTANT: Must install 1 set of brick panels. The operation of this unit without brick panels is prohibited.
NOTE: Only materials such as, but not limited to durarock,
wonderboard and concrete board may be put on the front face
of this appliance. See speci c requirements under "Framing
and Finishing" section.