INSTALLATION
INSTALLATION
L676-NG1 SYSTEM DATA
Canada USA
Altitude 0 - 2000 ft
(0 - 610m)
0 - 2000 ft
(0 - 610m)
Min. Supply
Pressure
5" WC (1.25
kpa)
5" WC
(1.25 kpa)
Low Setting Man.
Pressure
1.6" WC
(0.39 kpa)
1.6" WC
(0.39 kpa)
Max. Manifold
Pressure
3.5" WC
(0.87 kpa)
3.5" WC
(0.87 kpa)
Ori ce Size #33 DMS #33 DMS
Minimum Input 22,000 Btu/h
(6.45 kW)
22,000
Btu/h
(6.45 kW)
Maximum Input 33,000 Btu/h
(9.67 kW)
33,000
Btu/h
(9.67 kW)
Altitude 2000-4500
ft.
(610-1371m)
2000-4500
ft.
(610-
1371m)
Ori ce Size #33 DMS # 34 DMS
Minimum Input 22,000 Btu/h
(6.45 kW)
21,500
Btu/h
(6.30 kW)
Maximum Input 33,000 Btu/h
(9.67 kW)
32,000
Btu/h
(9.37kW)
L676-LP1 SYSTEM DATA
Altitude 0-4500 ft.
(0 - 1371m)
0-4500 ft.
(0 - 1371m)
Min. Supply
Pressure
12" WC
(2.98 kpa)
12" WC
(2.98 kpa)
Low Setting Man.
Pressure
6.4" WC
(1.59 kpa)
6.4" WC
(1.59 kpa)
Max. Manifold
Pressure
10" WC
(2.49 kpa)
10" WC
(2.49 kpa)
Ori ce Size #51 DMS #51 DMS
Minimum Input 25,000 Btu/h
(7.33 kW)
25,000
Btu/h
(7.33 kW)
Maxiumm Input 31,500 Btu/h
(9.23 kW)
31,500
Btu/h
(9.23 kW)
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8" wide at screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON"
position.
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits speci ed on the safety
label.
6) When nished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" at screwdriver.
Note: Screw should be snug, but do not
over tighten.
SIT 829 VALVE DESCRIPTION
1) Gas on/off knob
2) Electronically Operated Hi/Lo
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection Point
HIGH ELEVATION
This unit is approved in Canada for altitude 0
to 4500 ft. (CAN1 2.17-M91).
GAS LINE
INSTALLATION
Since some municipalities have additional
local codes it is always best to consult with
your local authorities and the CAN/CGA B149
installation code.
PILOT ADJUSTMENT
Periodically check the pilot ames. Correct
ame pattern has three strong blue ames:
1 owing around the thermopile, 1 around
the thermocouple and 1 owing across the
burner (it does not have to be touching the
burner).
Note: If you have an incorrect ame pattern,
contact your Regency
®
dealer for
further instructions.
Incorrect ame pattern will have small,
probably yellow ames, not coming into
proper contact with the rear burner or
thermopile or thermocouple.
IMPORTANT: Always check for gas leaks
with a soap and water solution or gas leak
detector. Do not use open ame for leak
testing.
For USA installations follow local codes and/
or the current National Fuel Gas Code, ANSI
Z223.1.
When using copper or ex connectors use only
approved ttings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and ex
connectors are usually considered to meet this
requirement.