L676-1 Direct Vent Gas Fireplace 15
INSTALLATION
INSTALLATION
VENTING ARRANGEMENTS
HORIZONTAL TERMINATION (FLEX)
Regency
®
Direct Vent System
These venting systems, in combination with the L676-1, have been tested and listed as a direct vent system by Warnock Hersey. The location of the
termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the
parts needed to install the L676-1 using a fl exible vent.
Notes:
1) Liner sections should be continuous without any joints
or seams.
2) Only Flex pipe purchased from FPI may be used for Flex
installations.
3) Horizontal vent must be supported every 3 feet.
4) A wall thimble is mandatory for all horizontal terminations
due to high temperatures.
FPI Kit # Length Contains:
#946-615 4 Feet 1) 8” fl exible liner (Kit length)
2) 5” fl exible liner (Kit length)
3) spring spacers
4) thimble
5) AstroCap termination cap
6) screws
7) tube of Mill Pac
8) plated screws
9) S.S. screws #8 x 1-1/2” drill point
10) vinyl siding standoff
#946-618 6 Feet
#946-616 10 Feet