Regency L676-1 Indoor Fireplace User Manual


 
Regency
®
L676-1 Direct Vent Gas Fireplace
22
INSTALLATION
VENTING ARRANGEMENTS
ALLOWABLE VERTICAL TERMINATIONS
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90
o
elbows, with
Rigid Pipe Venting Systems for Propane and Natural Gas. Two 45
o
elbows equal to one 90
o
elbow. Maximum of four 45
o
elbows allowed.
Vent must be supported at offsets.
Firestops are required at each oor level and whenever passing through a wall.
Maintain clearances to combustibles as listed in the "Clearances" section.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting
of Set 1 to Set 2 or Set 3 if required.
Note: Must use optional ue adapter when using Rigid Pipe (Part # 770-994).
INSTALLATION