L676-1 Direct Vent Gas Fireplace 19
INSTALLATION
VENTING ARRANGEMENTS
ALLOWABLE HORIZONTAL TERMINATIONS
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
o
two 45
o
elbows equal one 90
o
elbow).
Note: Must use optional rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems.
• Maintain clearances to combustibles as listed in "Clearances" section
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.
• A wall thimble is mandatory for all horizontal terminations due to high temperatures.
VENT RESTRICTOR SETTING:
Vent restrictor factory set, no adjustment required unless otherwise indicated.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 1 to
Set 2 or Set 4 if required.
Note: Regency
®
Direct Vent System (Flex) is only approved for horizontal terminations.