Heatiator BIR42 Indoor Fireplace User Manual


 
23
Outside Air
Hood
2 Wire Ties
Flexible Duct
(not supplied)
Figure 7.5 Outside Air Installation
E. Install Outside Air Kit
• Keep duct runs short and straight to minimize
restriction.
• Theoutsideairkitsmustbeinstalledonbothsidesofthe
replace.
WARNING! Outside air kits must be installed on both
sides of the replace to prevent overheating and re.
• Locatetheoutsideairhoodsinacleararea.
• InstallasshowninFigures7.3,7.4and7.5.
• Theairductsmayberunvertically.
• Theoutsideairhoodsmustbeatleast3ft(.91m)below
thetopoftheuppermostchimneysection.
• Theoutsideairhoodscanbepaintedtomatch/accentthe
colorofthestructure.
CAUTION! Risk of Fire or Asphyxiation! Do not draw
outside combustion air from wall, oor or ceiling cavity,
or enclosed spaces such as an attic or garage.
 place outside air hood close to exhaust
vents or chimneys. Fumes or odor could be drawn
into the room through the replace.
Locate outside air hood to prevent blockage from
leaves, snow/ice, or other debris. Blockages could
cause the unit to overheat.
NOTICE: The fireplace provides some outside air for
combustion. Other methods may be necessary if more air
is required.
Heatilator•BirminghamBIR42•4059-308RevJ•1/11