Model ERCH-HP Energy Recovery Unit
Installation
Model
Overall Exterior Dimensions
Width
(including Lifting Lugs)
Overall Width
(with Exhaust Hood)
Overall Length
(with Outdoor Air Hood)
ERCH-HP 20 59.5 75 116
ERCH-HP 45 69.5 86 122
ERCH-HP 55 79.5 101 134
ERCH-HP 90 99.5 123 147
All dimensions shown are in inches.
Unit Size U V
Approximate
Weight (pounds)
ERCH-HP 20 46 37 2150
ERCH-HP 45 54 39 3500
ERCH-HP 55 65 47 4450
ERCH-HP 90 85 49 5300
All dimensions are in inches. Unit weights assume rooftop
configuration with weatherhoods, filters, outdoor air damper,
six row DX coil, integral condensing section and an indirect
gas-fired furnace.
Supply
Discharge
Exhaust
Intake
U
V
1/2 inch 1/2 inch
1/2 inch
Position the unit roof opening such that the supply
discharge and exhaust inlet of the unit will line up with
the corresponding ductwork. Be sure to allow for the
recommended service clearances when positioning
opening (see Service Clearances). Do not face the
outdoor air intake of the unit into prevailing wind and
keep the intake away from any other exhaust fans.
Likewise, position the exhaust discharge opening away
from outdoor air intakes of any other equipment.
Unit Weights and Recommended Roof Opening
Dimensional Data