Goodman Mfg SS-CPH90-150 Air Conditioner User Manual


 
ProduCt SPeCifiCationS
ProduCt SPeCifiCationS
6 www.goodmanmfg.com SS-CPH90-150
ProduCt SPeCifiCationS — 12½ tonS
CPH150XXX
3BXXX
CPH150XXX
4BXXX
CPH150XXX
7BXXX
Cooling Capacity
Total, BTU/h 146,000 146,000 146,000
Sensible BTU/h 102,200 102,200 102,200
EER / IPLV 10.8 / 11.2 10.8 / 11.2 10.8 / 11.2
Decibels 83 83 83
ARI Reference #s 3554114 3554114 3554114
Heating Capacity
BTU/hr (47°F) 150,000 150,000 150,000
COP (47°F) 3.2 3.2 3.2
BTU/hr (17°F) 82,000 82,000 82,000
COP (17°F) 2.1 2.1 2.1
Evapoartor Motor / Coil
Motor Type (Belt Drive) AX49 AX49 AX49
Indoor Nominal CFM 5,000 5,000 5,000
Indoor Motor FLA (Cooling) 9.4 4.7 4.2
Horsepower - RPM 3.0 - 1,725 3.0 - 1,725 3.0 - 1,725
Piston Size (Cooling) 0.096 0.096 0.096
Filter Size (Qty) (4) 20" x 25" x 2" (4) 20" x 25" x 2" (4) 20" x 25" x 2"
Drain Size (NPT) ¾" ¾" ¾"
R-410A Refrigerant Charge Cir #1 & #2 (oz.) 290 / 290 290 / 290 290 / 290
Evaporator Coil Face Area (²) 14.7 14.7 14.7
Rows Deep / Fins per Inch 4 / 15 4 / 15 4 / 15
# of Wheels (D x W) (1) 15" x 15" (1) 15" x 15" (1) 15" x 15"
Motor Sheave / Blower Sheave VL40 / AK66 VL40 / AK66 VL40 / AK66
Condenser Fan / Coil
Quanty of condenser Fan Motors 2 2 2
Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075
Fan Diameter / # Fan Blades 22/ 3 22/ 3 22/ 3
Outdoor Nominal CFM 7,200 7,200 7,200
Face Area (²) 35.3 35.3 35.3
Rows Deep / Fins per Inch 2/3 rows 15 fpi 2/3 rows 15 fpi 2/3 rows 15 fpi
Piston Size (Heang) 0.067 0.067 0.067
Compressor
Quanty / Stage 2 / Single 2 / Single 2 / Single
Type Scroll Scroll Scroll
Compressor RLA / LRA ea. 22.4 / 149 10.6 / 75 7.7 / 54
Electrical Data / Static
Voltage / Phase / Frequency 208-230/ 3/ 60 460/ 3/ 60 575/ 3/ 60
Standard Max Stac 1.4" 1.4" 1.4"
Outdoor Fan FLA ea. 2.4 1.2 0.9
Total Unit Amps 59 28 21.4
Min. Circuit Ampacity¹ 65 31 23
Max. Overcurrent Protecon (amps)² 80 40 30
Entrance Power Supply
Locang
Dimple
Locang
Dimple
Locang
Dimple
Entrance Control Voltage
Operating Weight (lbs) 1325 1325 1325
Ship Weight (lbs) 1350 1350 1350
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.