SS-CPH90-150 www.goodmanmfg.com 25
48”
36” Min.
48”
48”
75”
unit clearanceS
electrical entrance locationS
11⅝”
10
3
/
16
3”
Low-Voltage Entrance
High-Voltage Entrance
Dimples Mark Drill Locaons
Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit
operation. Leave a total clearance of 75” on the main control panel side of the unit for possible removal
of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48” on all other sides of the unit for
possible compressor removal or service access, and to ensure proper
ventilation and condenser airow. Do not install the unit beneath
any obstruction. Install the unit away from all building
exhausts to inhibit ingestion of exhaust air into the unit’s
fresh-air intake.