Goodman Mfg SS-CPH90-150 Air Conditioner User Manual


 
ProduCt SPeCifiCationS
ProduCt SPeCifiCationS
SS-CPH90-150 www.goodmanmfg.com 19
airflow data — 12½ tonS
Standard Belt Drive --- Down Shot
ESP (in
W.C.)
Turns Open
0 1 2 3 4 5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 5378 2.35 4967 1.92 4710 1.59 4512 1.33
0.4 5514 2.92 5349 2.56 4750 1.97 4583 1.71 4319 1.40 4030 1.13
0.6 5204 2.69 4919 2.27 4488 1.81 4258 1.54
0.8 4830 2.42 4649 2.09 4019 1.55
1.0 4497 2.19 4264 1.86
High-Static Belt Drive --- Down Shot
ESP (in
W.C.)
Turns Open
0 1 2 3 4 5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.8 5978 3.87 5691 3.38 5324 2.81
1.0 5947 4.16 5656 3.58 5376 3.12 4933 2.52
1.2 5708 3.93 5459 3.40 4950 2.79 4441 2.18
1.4 5776 4.64 5510 4.07 5245 3.48 4844 2.88 4525 2.45
1.6 5465 4.30 5199 3.74 4894 3.17 4404 2.54
1.8 5145 3.97 4871 3.41 4495 2.83
2.0 4805 3.63 4565 3.13 4142 2.55
2.2 4429 3.27 4233 2.85
Standard Belt Drive --- Horizontal
ESP (in
W.C.)
Turns Open
0 1 2 3 4 5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 5570 2.27 4935 1.70 4584 1.36
0.4 5871 3.20 5639 2.77 5307 2.31 4902 1.88 4637 1.55 4178 1.19
0.6 5610 3.00 5358 2.57 5051 2.15 4603 1.72 4341 1.41
0.8 5391 2.83 5010 2.33 4799 2.00 4393 1.61
1.0 5078 2.59 4676 2.11 4448 1.79
1.2 4521 2.20 4226 1.83
High-Static Belt Drive --- Horizontal
ESP (in
W.C.)
Turns Open
0 1 2 3 4 5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.8 5858 3.51 5538 2.97
1.0 5894 3.85 5502 3.20 5282 2.78
1.2 5780 4.04 5570 3.55 5110 2.88 4869 2.47
1.4 5900 4.49 5501 3.77 5312 3.33 4793 2.64 4598 2.28
1.6 5860 4.76 5514 4.08 5257 3.54 4945 3.01 4382 2.34
1.8 5615 4.49 5315 3.88 5020 3.32 4504 2.66
2.0 5529 4.40 4906 3.49 4601 2.96
2.2 4938 3.78 4541 3.15 4222 2.65
Notes
Assume dry coil with lter in place; CFM correcon for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applicaon