Goodman Mfg SS-CPH90-150 Air Conditioner User Manual


 
Product SPecificationS
Product SPecificationS
26 www.goodmanmfg.com SS-CPH90-150
roof curb inStallation — rigging
Provisions for forks have been included in the unit base frame. No other
fork locations are approved.
• Unit must be lifted by the four lifting holes located at the base
frame corners.
• Lifting cables should be attached to the unit with shackles.
• The distance between the crane hook and the top of the unit must
not be less than 60”.
• Two spreader bars must span over the unit to prevent damage to
the cabinet by the lift cables. Spreader bars must be of sucient
length so that cables do not come in contact with the unit during
transport. Remove wood struts mounted beneath unit base frame
before setting unit on roof curb. These struts are intended to protect
unit base frame from fork lift damage. To remove the struts, extract
the sheet metal retainers and pull the struts through the base of the
unit. Refer to rigging label on the unit.
Important: If using bottom discharge with roof curb, duct-work
should be attached to the curb prior to installing the unit. Duct-work
dimensions are shown in Roof Curb Installation Instructions Manual.
Refer to the Roof Curb Installation Instructions
for proper curb installation. Curbing must
be installed in compliance with the National
Roong Contractors Association Manual.
Lower unit carefully onto roof mounting curb.
While rigging the unit, the center of gravity will
cause the condenser end to be lower than the
supply air end.
Bring condenser end of unit into alignment
with the curb. With condenser end of the
unit resting on curb member and using curb
as a fulcrum, lower opposite end of the unit
until entire unit is seated on the curb. When a
rectangular cantilever curb is used, take care
to center the unit. Check for proper alignment
and orientation of supply and return openings
with duct.
Note: These weights are calculated without accessories installed.
Corner & Center-of-Gravity Locations
30”
Compressor 1
Return
Evaporator Coil
Supply
Compressor 2
49”
Unit Weights
7½-Ton
Weights (lbs)
8½-Ton
Weights (lbs)
10-Ton
Weights (lbs)
12½-Ton
Weights (lbs)
Weight A 285 345 345 435
Weight B 285 325 325 345
Weight C 285 320 320 300
Weight D 285 300 300 240
Shipping Weight 1175 1310 1310 1350
Operang Weight 1135 1285 1285 1325