Change during operation: N = impossible, Y* = possible (enabled by using ),
Y
= possible (enabled by using
)
-
48
-
FUNC
DATA
DC injection brake
(starting frequency)
This function sets 3.0Hz (fixed) as the starting frequency of DC injection brake.
DC injection brake (Braking level)
This function sets a DC brake current level.
Levels can be set in 1% unit by assuming the level of the drive rated current to be 100%.
DC injection brake(Braking time)
This function sets the DC injection
braking time.
0.0 : No DC injection braking
0.1 to 30.0 : DC injection braking time 0.1
to 30s (in 0.1s step)
!
CAUTION
Do not use the drive brake function for
mechanical holding,
otherwise injuries could occur.
Output Freq.
3Hz
Time
Output voltage
DC injection brake
Factory
setting
Change during
operation
3.0Hz
N
F20
F21
F22
Factory
setting
Change during
operation
0%
Y
Factory
setting
Change during
operation
0.0s
Y