GE C11 Sewing Machine User Manual


 
-
22
-
Classifi-
cation
Termi-
nal
symbol
Terminal name Detailed specifications Remarks
Analog
output
FM, 11 Analog monitor Data selected between the following items is
output with DC voltage:
Output frequency
PID feedback value
Output current
DC link circuit voltage
* Up to two analog voltmeters (input imped-
ance : 10 k can be connected.
Note: Output waveform: An AC pulse is out-
put with consistent frequency and variable
duty. The average DC voltage is proportional
to output frequency and output current (fre-
quency : 121.6 Hz).
Contact
output
30A
30B
30C
Alarm output for any
fault
If the drive is stopped with an alarm, the
non-voltage contact signal (SPDT) is output
(Contact rating: 250V ac, 0.3 A, Power factor
= 0.3)
(48V dc, 0.5A for Low-voltage Directive or
42V dc, 0.5A for UL/cUL)
Whether an alarm is generated with an excit-
ing operation or non-exciting operation can
be switched.
Optional
DX+
DX
RS485 RTU commu-
nication input/output
Terminal for RS485 communication (when
option board is installed)
DX+ : Non-inverted signal,
DX : Inverted signal
Installed on op-
tional board.