FMI CGCFTNA Indoor Fireplace User Manual


 
www.fmiproducts.com
124978-01B8
WARNING: If the area in which


-


  National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,



This fresh air would come from an adjoining
unconned space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 4). You can also remove door
into adjoining room (see option 3, Figure 4).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
AIR FOR COMBUSTION AND VENTILATION
Continued

Provide extra fresh air by using ventilation
grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
Figure 5 - Ventilation Air from Outdoors
Shown with Optional Mantel
Outlet
Air
V entilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
V entilated
Crawl Space
T o
Crawl
Space
T o Attic
Figure 4 - Ventilation Air from Inside
Building Shown with Optional Mantel
Or
Remove
Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills into
Adjoining
Room,
Option 1