Enviro 50-1040 Stove User Manual


 
23
Installation
OUTSIDE AIR KIT:
It is mandatory to use outside air for installations in mobile homes.
A 4” (10.2 cm) fresh air adaptor kit is available. This adaptor can be
installed either on the back pedestal or through the oor under the
pedestal. The cover plate must be installed on the unit if your stove is
located in a mobile home or if using outside air from the bottom.
Place the ” mesh screen between the fresh air adaptor and the body of
the pedestal (as shown to right).
NOTE: Fresh air connection to the unit must be a non-combustible pipe,
example: 4” (10.2 cm) single wall aluminum ex pipe.
NOTE: Remove the cover plate on the rear of the pedestal if room air is to be used for combustion air.
RECOMMENDED HEIGHTS FOR FLUE PIPE:
The minimum ue pipe height at sea level is 12 feet (3.7 m) straight up from top of the unit. For every
1000 feet (305 m) above sea level, 4% must be added to the overall height. Use Tables 7, 8, and 9 to
calculate the required vertical rise required.
Elevation
above sea
level
Minimum recommended ue pipe height for # of elbows
(Note: No more than 2 offsets (4 elbows) can be used. 2x45°=1x90°
feet 0 2 x 15° 4 x 15° 2 x 30° 4 x 30° 2 x 45° 4 x 45°
0-1000 12.0 12.7 13.3 13.3 14.7 14.0 16.0
1000-2000 12.5 13.2 13.8 13.8 15.3 14.6 16.6
2000-3000 13.0 13.7 14.4 14.4 15.9 15.1 17.3
3000-4000 13.4 14.2 14.9 14.9 16.5 15.7 17.9
4000-5000 13.9 14.7 15.4 15.4 17.1 16.2 18.6
5000-6000 14.4 15.2 16.0 16.0 17.6 16.8 19.2
6000-7000 14.9 15.7 16.5 16.5 18.2 17.4 19.8
7000-8000 15.4 16.3 17.0 17.0 18.8 17.9 20.5
8000-9000 15.8 16.8 17.6 17.6 19.4 18.5 21.1
9000-10000 16.3 17.3 18.1 18.1 20.0 19.0 21.8
meters 0 2 x 15° 4 x 15° 2 x 30° 4 x 30° 2 x 45° 4 x 45°
0-305 3.7 3.9 4.1 4.1 4.5 4.3 4.9
305-610 3.8 4.0 4.2 4.2 4.6 4.4 5.1
610-915 4.0 4.2 4.4 4.4 4.8 4.6 5.3
915-1220 4.1 4.3 4.6 4.6 5.0 4.8 5.5
1220-1525 4.2 4.5 4.7 4.7 5.2 4.9 5.7
1525-1830 4.4 4.6 4.9 4.9 5.4 5.1 5.9
1830-2135 4.5 4.8 5.0 5.0 5.5 5.3 6.0
2135-2440 4.7 4.9 5.2 5.2 5.7 5.5 6.2
2440-2745 4.8 5.1 5.4 5.4 5.9 5.6 6.4
2745-3050 5.0 5.3 5.5 5.5 6.1 5.8 6.6
 
Figure 19: Fresh Air Adaptor
onto the Back of the Pedestal.
Distance to add
Part used feet meters
45° elbow 1.0 0.3
90° elbow 2.0 0.6
“T” 3.0 0.9
1 foot
(0.3m) of
horizontal
run
2.0 0.6
Height
sea level with 2
x 30° elbows
13.3 ft (4.1 m)
one “T” 3.0 ft (0.9 m)
1 ft (0.6 m)
horizontal run
3.0 ft (0.9 m)
Total 1 19.3 ft (5.9 m)
4000-5000 ft
(1220-1525 m)
above sea level
13.9 ft (4.2 m)
one “T” 3.0 ft (0.9 m)
2 ft (0.6 m)
horizontal run
4.0 ft (1.2 m)
Total 2 20.9 ft (6.3 m)
Table 9: Recommended Height for Flue Pipe.
Table 10: Distance to add to
overall vertical height.
Table 11: Examples of calculating
overall vertical height required.