Empire Comfort Systems DVP48FP3 Water Heater User Manual


 
Page 16 17375-6-0705
MAXIMUM HORIZONTAL
RUN WITH NO VERTICAL
RISE AND 90° ELBOW
MAXIMUM HORIZONTAL
RUN WITH MINIMUM
VERTICAL RISE AND
90° ELBOW
minimum
Figure 25
Figure 24
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH THE
WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE ELBOW
OFF TOP OF FIREPLACE
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent termination
will be centered (if possible) between two (2) studs. This will avoid any
extra framing. All vent kit pipes should be assembled on the unit after
the unit is moved into the final position.
Cutting the Hole (Figures 23)
After the fireplace has been positioned in its permanent location, the hole
through the exterior wall of the house can be cut. This hole must be 12"
(305mm) high x 10" (254mm) wide with its center line determined by the
amount of vertical rise and horizontal run of the termination. (See Figure
23) When locating the hole it must be noted that the bottom of the cap
must be 12" (305mm) above the ground level, and top of the cap must
be no less than 18" (457mm) below a combustible projection, and no
closer than 9" (229mm) to any wall running parallel to vent termination.
(See Figure 24)
A
CENTER
OF
ELBOW
STRAIGHT
OUT
(MINIMUM)
2
30
FIREPLACE
SERIES
HARD ELBOW DIMENSIONS
"A" "B" "C"
DVP42FP 43-1/2"
(1105mm)
5"
(127mm)
7"
(178mm)
DVP48FP 43-1/2"
(1105mm)
5"
(127mm)
7"
(178mm)
FIREPLACE
SERIES
FLEX PIPE 90 DEGREE BEND
"A" "B" "C"
DVP42FP 46"
(1143mm)
5"
(127mm)
7"
(178mm)
DVP48FP 46"
(1143mm)
5"
(127mm)
7"
(178mm)
Figure 23