Carrier PCV015-060 Heat Pump User Manual


 
30
Table 20 — 50PC042 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 21 — 50PC048 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 22 — 50PC060 Typical Unit Operating Pressures and Temperatures
LEGEND
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
COOLING HEATING
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5 114-124 170-190 27-32 10-15 17.2-19.2 17-23 69- 79 286-306 5-10 5-10 4.5- 6.5 16-22
2.25 113-123 150-170 27-32 9-14 12.7-14.7 17-23 72- 82 289-309 5-10 6-11 3.9- 5.9 17-23
3 113-123 131-151 27-32 7-12 8.2-10.2 17-23 75- 85 292-312 6-11 6-11 3.2- 5.2 18-24
50
1.5 130-140 226-246 10-15 6-11 17.8-19.8 20-26 100-110 315-335 7-12 6-11 9.0-11.0 22-28
2.25 129-139 208-228 10-15 5-10 13.3-15.3 20-26 105-115 322-342 8-13 6-11 7.0- 9.0 23-29
3 129-139 190-210 10-15 4- 9 8.8-10.8 20-26 110-120 330-350 10-15 7-12 5.0- 7.0 24-30
70
1.5 132-142 290-310 6-11 6-11 17.3-19.3 19-25 131-141 347-367 11-16 6-11 13.4-15.4 29-35
2.25 131-141 273-293 6-11 5-10 12.8-14.8 19-25 138-148 358-378 13-18 8-13 10.0-12.0 30-36
3 131-141 255-275 6-11 4- 9 8.3-10.3 19-25 145-155 369-389 16-21 9-14 6.9- 8.9 31-37
90
1.5 136-146 370-390 6-11 6-11 16.0-18.0 17-23 175-185 393-413 19-24 7-12 17.6-19.6 36-42
2.25 135-145 350-370 6-11 5-10 11.8-13.8 17-23 177-187 401-421 20-25 9-14 13.2-15.2 37-43
3 135-145 330-350 6-11 4- 9 7.6- 9.6 17-23 180-190 409-429 22-27 12-17 8.7-10.7 38-44
110
1.5 143-153 469-489 6-11 6-11 14.0-16.0 16-22
2.25 142-152 448-468 6-11 5-10 11.0-13.0 16-22
3 141-151 427-447 6-11 4- 9 7.0- 9.0 16-22
DB Dry Bulb
——No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
COOLING HEATING
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5 108-118 180-200 27-32 12-17 19.8-21.8 19-25 65- 75 293-313 7-12 9-14 8.2-10.2 17-23
2.25 107-117 161-181 28-33 10-15 14.8-16.8 19-25 68- 78 297-217 8-13 9-14 6.2- 8.2 18-24
3 107-117 142-162 29-34 9-14 9.8-11.8 19-25 72- 82 301-321 9-14 9-14 4.2- 6.2 19-25
50
1.5 123-133 236-256 16-21 8-13 20.2-22.2 21-27 92-102 321-341 10-15 11-16 11.6-13.6 23-29
2.25 122-132 218-238 17-22 7-12 15.2-18.2 21-27 100-110 330-350 11-16 11-16 8.9-10.9 24-30
3 122-132 200-220 17-22 6-11 10.2-12.2 21-27 108-118 340-360 12-17 11-16 6.0- 8.0 26-32
70
1.5 130-140 305-325 10-15 8-13 20.0-22.0 20-26 122-132 353-373 12-17 11-16 15.0-17.0 29-35
2.25 129-139 285-305 11-16 6-11 15.0-17.0 20-26 133-143 365-385 14-19 11-16 11.5-13.5 31-37
3 129-139 265-285 11-16 5-10 10.0-12.0 20-26 144-154 378-398 16-21 11-16 8.0-10.0 33-39
90
1.5 133-143 390-410 8-13 8-13 19.0-21.0 19-25 166-176 397-417 16-21 9-14 19.5-21.5 37-43
2.25 132-142 368-388 9-14 6-11 14.0-16.0 19-25 173-183 407-727 18-23 9-14 14.7-16.7 38-44
3 132-142 345-365 9-14 5-10 9.0-11.0 19-25 181-191 417-437 19-24 10-15 9.9-11.9 40-46
110
1.5 141-151 497-517 6-11 8-13 18.0-20.0 18-24
2.25 140-150 472-492 7-12 6-11 13.5-15.5 18-24
3 140-150 447-467 8-13 5-10 8.7-10.7 18-24
DB Dry Bulb
——No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
COOLING HEATING
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5 98-108 160-180 40-45 12-17 20.0-22.0 19-25 62- 72 276-296 6-11 6-11 8.0-10.0 17-23
2.25 97-107 149-169 41-46 12-17 14.3-16.3 19-25 66- 76 280-300 6-11 6-11 6.0- 8.0 18-24
3 96-106 137-157 42-48 11-16 8.5-10.5 20-26 70- 80 284-304 7-12 6-11 4.0- 6.0 19-25
50
1.5 118-128 225-245 36-41 11-16 21.2-23.2 19-25 88- 98 306-326 10-15 8-13 11.0-13.0 23-29
2.25 117-127 210-230 37-42 10-15 15.7-17.7 20-26 94-104 311-331 10-15 8-13 8.3-10.3 24-30
3 115-125 195-215 38-43 9-14 10.2-12.2 21-27 100-110 317-337 11-16 9-14 5.5- 7.5 25-31
70
1.5 135-145 300-320 12-17 9-14 20.3-22.3 21-27 112-122 333-353 12-17 10-15 14.0-16.0 28-34
2.25 133-143 285-305 14-19 8-13 15.0-17.0 21-27 122-132 342-362 14-19 10-15 10.5-12.5 30-36
3 132-142 270-290 16-21 7-12 10.0-12.0 22-28 130-140 351-371 15-20 11-16 7.3- 9.3 32-38
90
1.5 139-149 390-410 8-13 7-12 19.3-21.3 20-26 147-157 369-389 15-20 10-15 17.7-19.7 36-42
2.25 138-148 370-390 8-13 6-11 14.3-16.3 21-27 154-164 377-397 18-23 10-15 13.4-15.4 37-43
3 138-148 350-370 8-13 6-11 9.3-11.3 21-27 160-170 385-405 19-24 11-16 9.0-11.0 38-44
110
1.5 144-154 488-508 8-13 8-13 18.4-20.4 21-27
2.25 143-153 468-488 7-12 6-11 13.6-15.6 21-27
3 142-152 448-468 7-12 5-10 8.8-10.8 21-27
DB Dry Bulb
——No Heating Operation in This Temperature Range