Carrier PCV015-060 Heat Pump User Manual


 
29
Table 17 — 50PC024 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 18 — 50PC030 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 19 — 50PC036 Typical Unit Operating Pressures and Temperatures
LEGEND
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
COOLING HEATING
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5 115-125 154-174 40-45 8-13 16.5-18.5 19-25 73- 83 283-303 8-12 6-11 5.9- 7.9 16-22
2.25 115-125 141-161 40-45 6-11 12.1-14.1 20-26 75- 85 285-305 8-12 6-11 4.2- 6.2 17-23
3 115-125 127-147 40-45 6-11 77.7- 9.7 20-26 78- 88 287-307 8-12 6-11 2.7- 4.7 18-24
50
1.5 115-120 209-229 24-29 10-15 15.7-17.7 18-24 102-112 313-333 8-12 8-13 8.9-10.9 22-28
2.25 115-120 195-215 24-29 8-13 11.6-13.6 18-24 106-116 314-334 8-12 8-13 6.7- 8.7 23-29
3 115-120 181-201 24-29 8-13 7.6- 9.6 18-24 110-120 316-336 8-12 8-13 4.5- 6.5 23-29
70
1.5 136-146 275-295 6-11 6-11 15.7-17.7 18-24 128-138 340-360 9-14 9-14 11.3-13.3 27-34
2.25 136-146 261-281 6-11 5-10 11.6-13.6 18-24 134-144 342-362 9-14 9-14 8.5-10.5 28-35
3 136-146 247-267 6-11 4- 9 7.6- 9.6 18-24 141-151 344-364 9-14 9-14 5.8- 7.8 28-35
90
1.5 140-150 361-381 6-11 6-11 14.9-16.9 18-24 162-172 370-390 14-19 9-14 14.4-16.4 32-40
2.25 140-150 347-367 6-11 5-10 11.0-13.0 18-24 166-176 376-396 15-20 9-14 10.8-12.8 34-42
3 140-150 333-353 6-11 4- 9 7.2- 9.2 18-24 171-181 383-403 16-21 9-14 7.1- 9.1 34-42
110
1.5 144-154 460-480 6-11 6-11 13.9-15.9 17-23
2.25 144-154 445-465 6-11 4- 9 10.2-12.2 17-23
3 144-154 428-448 6-11 4- 9 6.5- 8.5 17-23
DB Dry Bulb
——No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
COOLING HEATING
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5 116-126 146-166 27-32 7-13 19.6-21.6 16-22 69- 79 275-295 7-12 6-11 7.2- 9.2 16-22
2.25 115-125 138-158 27-32 6-11 14.3-16.3 17-23 73- 83 277-297 7-12 6-11 5.4- 7.4 17-23
3 115-125 128-148 27-32 6-11 8.0-10.0 17-23 76- 86 279-299 7-12 6-11 3.5- 5.5 17-23
50
1.5 129-139 217-237 12-17 6-11 20.8-22.8 17-23 96-106 300-320 10-15 9-14 10.5-12.5 21-27
2.25 128-138 203-223 12-17 5-10 15.0-17.0 18-24 100-110 304-324 10-15 9-14 7.6- 9.6 22-28
3 128-138 189-209 12-17 5-10 9.2-11.2 18-24 105-115 309-329 10-15 9-14 4.8- 6.8 22-28
70
1.5 132-142 293-313 9-14 6-11 20.1-22.1 17-23 123-133 327-347 11-16 11-16 13.2-15.2 25-32
2.25 131-141 274-294 9-14 5-10 14.4-16.4 18-24 129-139 333-353 11-16 11-16 9.8-11.8 26-33
3 131-141 256-276 9-14 5-10 8.6-10.6 18-24 135-145 339-359 11-16 11-16 6.4- 8.4 27-34
90
1.5 137-147 383-403 7-12 5-10 19.4-21.4 16-22 155-165 355-375 13-18 11-16 16.8-18.8 30-38
2.25 137-147 362-382 7-12 5-10 13.8-15.8 16-22 162-172 362-382 14-19 11-16 12.7-14.7 31-39
3 137-147 342-362 7-12 5-10 8.2-10.2 16-22 169-179 369-389 16-21 11-16 8.6-10.6 32-40
110
1.5 143-153 475-495 6-11 9-14 18.2-20.2 16-22
2.25 143-153 457-477 6-11 6-11 13.0-14.0 16-22
3 143-153 439-459 6-11 6-11 7.7- 9.7 16-22
DB Dry Bulb
——No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
COOLING HEATING
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5 117-127 142-162 33-38 8-14 19.1-21.1 15-22 69- 79 276-296 10-15 10-15 7.2- 9.2 17-23
2.25 116-126 134-154 33-38 7-12 13.8-15.8 15-22 73- 83 278-298 10-15 10-15 5.3- 7.3 18-24
3 116-126 124-144 33-38 7-12 7.4- 9.4 15-22 76- 86 280-300 10-15 10-15 3.5- 5.5 18-24
50
1.5 136-146 211-231 11-16 6-11 20.6-22.6 17-23 99-109 302-322 10-15 13-18 10.6-12.6 22-28
2.25 136-146 197-217 11-16 5-10 14.8-16.8 17-23 103-113 306-326 10-15 13-18 7.7- 9.7 23-29
3 136-146 183-203 11-16 5-10 9.0-11.0 17-23 108-118 311-331 10-15 13-18 5.0- 7.0 23-29
70
1.5 137-147 275-295 9-14 10-15 19.0-21.0 18-24 127-137 332-352 10-15 15-20 13.5-15.5 27-34
2.25 137-147 260-280 9-14 9-14 13.8-15.8 19-25 133-143 338-358 10-15 15-20 10.1-12.1 28-35
3 137-147 245-265 9-14 9-14 8.0-10.0 19-25 139-149 344-364 10-15 15-20 6.7- 8.7 29-36
90
1.5 142-152 373-393 7-12 10-15 19.5-21.5 17-23 164-174 365-385 11-16 15-20 17.4-19.4 34-42
2.25 142-152 352-372 8-13 6-11 13.9-15.9 17-23 172-182 372-392 11-16 15-20 13.2-15.2 35-43
3 142-152 332-352 8-13 6-11 8.3-10.3 17-23 181-191 379-399 12-17 15-20 9.0-11.0 36-44
110
1.5 147-157 467-487 6-11 10-15 16.2-18.2 16-22
2.25 147-157 448-468 6-11 8-13 11.9-13.9 16-22
3 147-157 430-450 6-11 7-12 7.6- 9.6 16-22
DB Dry Bulb
——No Heating Operation in This Temperature Range