Carrier MPE62L-10R Heating System User Manual


 
UNIT SIZE
48MPD,E
WEIGHT A B C D E F
lb kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.
62L 16,810 7624 3505 11- 6 957 3-1
11
16
5909 19-4
5
8
1203 3-11
3
8
13 011 42-8
1
4
14 256 46-9
1
4
70M 18,060 8190 3647 11-11
9
16
1165 3-9
7
8
6166 20-2
3
4
1264 4- 1
3
4
13 297 43-7
1
2
14 542 47-8
1
2
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Centerof gravityincludesexhaust fanandhigh heatoptions.Unitweight doesnotinclude exhaustfanor high
heat options.
3. High heat add: 260 lb [118 kg]
Exhaust fan add: 1675 lb [761 kg] on 62L
1775 lb [807 kg] on 70M
4. Unit clearances:
Top — Do not restrict condenser fans, control box end — 6Ј-0Љ.
Sides — 6Ј-0Љ (except on return fan equipped units — 10Ј-0Љ).
Economizer end — 6Ј-0Љ (except power exhaust units — 10Ј-0Љ).
For smaller service and operational clearances, contact Carrier Application Engineering Department.
5. Downshotducts designedto beattached toaccessory roofcurb. Ifunit ismounted ondunnage, itis recommended
the ducts be supported by cross braces as done on the accessory roof curb.
Fig. 3 Base Unit Dimensions, 48MP62L, 70M
9