Bryant 581J Heating System User Manual


 
21
Perfect Humidityt Control Connections
Perfect Humidity -- Space RH Controller —
NOTE: Perfect Humidity is a factory installed option
which is only available for units equipped with belt--drive
motors.
The Perfect Humidity dehumidification system requires a
field--supplied and --installed space relative humidity
control device. This device may be a separate humidistat
control (contact closes on rise in space RH above control
setpoint) or a combination thermostat--humidistat control
device such as Bryant’s EDGE
R
Pro Thermidistat with
isolated contact set for dehumidification control. The
humidistat is normally used in applications where a
temperature control is already provided (such as a
third--party Building Management System).
To connect a field--supplied humidistat:
1. Route the humidistat 2--conductor cable (field--sup-
plied) through the hole provided in the unit corner
post.
2. Feed wires through the raceway built into the corner
post (see Fig. 30) to the 24--v barrier located on the
left side of the control box. The raceway provides the
UL--required clearance between high--voltage and
low--voltage wiring.
3. Use wire nuts to connect humidistat cable to two
PINK leads in the low–voltage wiring as shown in
Fig. 32. Refer to the instructions for the field--sup-
plied humidistat for more information.
To connect the Edge Programmable Thermidistat
(T6--PRH01--A):
1. Route the Edge Programmable Thermostat multi--
conductor cable (field--supplied) through the hole
provided in the unit corner post.
2. Feed wires through the raceway build into the corner
post (see Fig. 30) to the 24--v barrier located on the
left side of the control box. The raceway provides the
UL--required clearance between high--voltage and
low--voltage wiring.
3. The Edge Programmable Thermostat has dry contacts
at terminals D1 and D2 for dehumidification
operation (see Fig. 33). The dry contacts must be
wired between CTB terminal R and the PINK lead to
the LTLO switch with field--supplied wire nuts. Refer
to the installation instructions included with the
Bryant Edge Programmable Thermidistat device for
more information.
C09502
Fig. 31 -- Edge Programmable Thermostat
581J