Bryant 559F Air Conditioner User Manual


 
PKG.
NO. REF.
CURB
HEIGHT
DESCRIPTION
308450-201
1Ј-2Љ
(305)
Standard Curb
14Љ High
308450-202
2Ј-0Љ
(610)
Standard Curb
for Units
Requiring High
Installation
308450-203
2Ј-0Љ
(610)
Side Supply
and Return Kit
for High Installation
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels:
1
2
Љ thick neoprene coated 2 lb density.
3. Dimensions in ( ) are in millimeters.
4. Direction of airflow.
5. Roof curb: 16 ga. (VA03-56) stl.
NOTE: To prevent the hazard of stagnant water build-up in the drain pan of the
indoor section, unit can only be pitched as shown.
UNIT LEVELING TOLERANCES*
Dimensions (degrees and inches)
UNIT
AB
DEG. IN. DEG. IN.
559F .28 .45 .28 .43
*From edge of unit to horizontal.
Fig. 1 Roof Curb Details
—2—