Bryant 559F Air Conditioner User Manual


 
Table 2 Electrical Data (cont)
UNIT
559F
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM IFM
POWER
EXHAUST
ELECTRIC
HEAT*
POWER
SUPPLY
No. 1 No. 2
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA kW FLA MCA MOCP†
300
(25 Tons)
208/230 187 253 41.0 350 37.8 239 2 1 6.6 10.0 28.0/28.0
130/130 150/150
4.6 18.8 135/135 175/175
26/34 71/82 130/138 150/150
4.6 18.8 26/34 71/82 135/143 175/175
42/56 117/135 181/170 200/175
4.6 18.8 42/56 117/135 187/176 200/200
56/75 156/180 191/215 200/225
4.6 18.8 56/75 156/180 197/221 200/225
460 414 508 21.8 158 17.2 125 2 1 2.8 10.0 14.6
66 80
2.3 6.0 68 80
32 39 67 80
2.3 6.0 32 39 70 80
55 66 84 90
2.3 6.0 55 66 87 100
80 96 114 125
2.3 6.0 80 96 117 125
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
and 480 v. Heaters are rated at 240 v and 480 v. If power distribution
voltage to unit varies from rated heater voltage, heater kW will vary
accordingly.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The Canadian units
may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
Use the following formula to determine the percent of voltage
imbalance.
% Voltage Imbalance =
max voltage deviation from average voltage
100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANTIf the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
3. MCA calculation for units with electric heaters over 50 kW
= (1.25 x IFM amps) + (1.00 x heater FLA).
—10—