Bryant 559F Air Conditioner User Manual


 
Table 7 Fan Performance 559F300
559F300 (25 TONS)
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
7,000 845 3.26 2693 909 3.60 2979 969 3.96 3272 1028 4.32 3574 1083 4.70 3883 1137 5.08 4,200
7,500 896 3.82 3156 956 4.17 3450 1014 4.54 3752 1069 4.91 4060 1123 5.29 4375 1174 5.68 4,698
8,000 948 4.43 3667 1005 4.80 3969 1060 5.17 4278 1112 5.56 4593 1163 5.94 4915 1213 6.34 5,243
8,500 1001 5.11 4226 1054 5.49 4537 1106 5.87 4853 1156 6.26 5175 1205 6.66 5504 1253 7.06 5,838
9,000 1053 5.85 4836 1104 6.23 5155 1154 6.63 5478 1202 7.02 5808 1248 7.43 6142 1294 7.84 6,483
9,500 1106 6.65 5498 1155 7.04 5824 1202 7.44 6155 1248 7.85 6492 1293 8.26 6833 1336 8.68 7,179
10,000 1159 7.52 6214 1206 7.92 6547 1251 8.33 6886 1295 8.74 7229 1338 9.16 7577 1380 9.59 7,929
10,500 1213 8.45 6984 1257 8.86 7325 1300 9.28 7671 1342 9.70 8020 1384 10.13 8375 1424 10.56 8,733
11,000 1266 9.45 7810 1309 9.87 8159 1350 10.29 8511 1391 10.73 8868 1431 11.16 9229 1470 11.60 9,594
11,250 1293 9.97 8245 1334 10.40 8597 1375 10.83 8953 1415 11.26 9313 1454 11.70 9677 1493 12.15 10,045
559F300 (25 TONS) (cont)
Airflow
(Cfm)
Available External Static Pressure (in. wg)
1.4 1.6 1.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
7,000 1189 5.47 4,524 1239 5.87 4,854 1288 4.91 5191
7,500 1224 6.08 5,026 1272 6.48 5,362 1320 5.56 5703
8,000 1261 6.75 5,577 1307 7.16 5,917 1353 6.26 6263
8,500 1299 7.47 6,177 1344 7.89 6,523 1388 7.02 6873
9,000 1338 8.26 6,828 1382 8.68 7,179 1424 7.85 7534
9,500 1379 9.11 7,530 1421 9.54 7,887 1462 8.74 8247
10,000 1421 10.02 8,286 1461 10.46 8,648 1501 9.70 9014
10,500 1464 11.00 9,096 1503 11.45 9,464 1541 10.73 9835
11,000 1508 12.05 9,963 1546 12.50 10,336
11,250 1530 12.60 10,417
LEGEND
Bhp Brake Horsepower
FIOP Factory-Installed Option
Watts Input Watts to Motor
NOTES:
1. Standard low-medium static drive range is 1066 to 1283 rpm. Alter-
nate high-static drive range is 1332 to 1550. Other rpms require a
field-supplied drive.
2. Maximum continuous bhp is 10.2 (208/230 v) or 11.8 (460 v) and the
maximum continuous watts are 9510 (208/230 v) or 11,000 (460 v).
Do not adjust motor rpm such that motor maximum bhp and/or watts
is exceeded at the maximum operating cfm.
3. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Fan Performance table.
4. Interpolation is permissible. Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and
casing losses. See Table 9 for accessory/FIOP static pressure
information.
6. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confi-
dence. Using your fan motors up to the watts or bhp rating shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
7. Use of a field-supplied motor may affect wiring size. Contact your
Bryant representative for details.