ARI* CAPACITY RATINGS (cont)
549C024-060
549B036-060
549B072-120
LEGEND
*Air Conditioning and Refrigeration Institute.
†Applies only to units with capacity of 60,000 Btuh or less.
NOTE: Rated in accordance with ARI Standard 210/240-94 and 270-
95. Ratings are net values, reflecting effects of circulating fan heat.
Supplementary electric heat is not included. Ratings based on:
Cooling Standard: 80 F db (dry bulb), 67 F wb (wet bulb) indoor enter-
ing-air temperature and 95 F db outdoor entering-air temperature.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and
80 F db outdoor entering-air temperature.
High-Temp Heating Standard: 70 F db indoor entering-air temperature
and 47 F db, 43 F wb outdoor entering-air temperature.
Low-Temp Heating Standard: 70 F db indoor entering-air temperature
and 17 F db, 15 F wb outdoor entering-air temperature.
ALL the 549B units are in compliance with ASHRAE 90.1 2001 Energy
Standard for minimum SEER and EER requirements. Refer to state and
local codes or visit the following website: http://solstice.crest.org/
efficiency/bcap to determine if compliance with this standard pertains to
a given geographical area of the United States.
542J150,180 UNITS
LEGEND
*Air-Conditioning and Refrigeration Institute.
NOTE: 50HJQ units are rated in accordance with ARI Standard 340-93.
Cooling ratings are net values, reflecting the effects of circulating fan
heat. Ratings are based on:
ESP: –.35 in. wg
Cooling Standard: 80 F db, 67 wb indoor coil entering-air temperature
and 95 F outdoor entering-air temperature.
High-Temp Heating Standard: 70 F db indoor coil entering-air temper-
ature and 47 F db, 43 F wb outdoor coil entering-air temperature.
Low-Temp Heating Standard: 70 F db indoor coil entering-air temper-
ature and 17 F db, 15 F wb outdoor coil entering-air temperature.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and
80 F db outdoor entering-air temperature.
ALL the 542J units are in compliance with ASHRAE 90.1 2001 Energy
Standard for minimum SEER and EER requirements. Refer to state and
local codes or visit the following website: http://solstice.crest.org/
efficiency/bcap to determine if compliance with this standard pertains to
a given geographical area of the United States.
UNIT
549C
NOMINAL
TONS
COOLING HEATING (High Temp)
SOUND
RATING
(decibels)
Net Cap.
(Btuh)
SEER†
Cap.
(Btuh)
HSPF†
024 2 24,000 14.0 23,600 8.10 76
036 3 37,000 14.0 36,000 8.10 76
048 4 46,000 14.0 46,000 8.00 76
060 5 58,500 14.0 58,000 8.00 80
UNIT
549B
NOMINAL
TONS
COOLING HEATING (High Temp)
SOUND
RATING
(decibels)
Net Cap.
(Btuh)
SEER†
Cap.
(Btuh)
HSPF†
036 3 35,600 13.1 34,800 7.7 76
048 4 45,000 13.0 45,000 7.8 76
060 5 58,000 13.0 55,000 7.7 80
UNIT
549B
NOMINAL
TONS
COOLING
HEATING
(High)
HEATING
(Low)
SOUND
RATING
(decibels)
IPLV
Net Cap.
(Btuh)
EER
Cap.
(Btuh)
COP
Cap.
(Btuh)
COP
072 6 71,000 10.5 69,000 3.4 37,000 2.2 80
090 7
1
/
2
88,000 10.3 85,000 3.3 48,000 2.2 82 10.5
102 8
1
/
2
98,000 10.3 96,000 3.3 52,000 2.2 110
12.7 (100%)
10.4 ( 50%)
120 10 116,000 10.3 103,000 3.3 64,000 2.2 84 10.4
Cap. Net Capacity (Btuh)
COP Coefficient of Performance
EER Energy Efficiency Ratio
HSPF Heating Seasonal Performance Factor
IPLV Integrated Part-Load Values
SEER Seasonal Energy Efficiency Ratio
UNIT
542J
COOLING HEATING-HIGH TEMP HEATING-LOW TEMP
SOUND
RATING
(decibels)
Total
kW
Net
Capacity
(Btuh)
Cfm IPLV EER
Total
Capacity
(Btuh)
Total
kW
COP
Total
Capacity
(Btuh)
Total
kW
COP
150 14.3 140,000 4500 12.4 9.8 136,000 12.4 3.2 72,000 10.0 2.1 87
180 18.5 172,000 5200 9.7 9.3 172,000 15.3 3.3 90,000 12.5 2.2 88
COP Coefficient of Performance
db Dry Bulb
EER Energy Efficiency Ratio
ESP External Static Pressure
IPLV Integrated Part-Load Value
wb Wet Bulb