Bryant 549C Heat Pump User Manual


 
126
ELECTRICAL DATA — 549B (cont)
549B036-120 — HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)
LEGEND
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If
power distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.
†Heaters are field installed only.
**Fuse or HACR circuit breaker.
††Electrical disconnect cannot be used if electric heater is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percentage of voltage
imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.
POWER EXHAUST ELECTRICAL DATA
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 549B060 unit with MCA = 35.6 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 35.6 amps + 1.6 amps = 37.2 amps
If the new MCA does not exceed the published MOCP, then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If “MCA New” is larger than the published
MOCP, raise the MOCP to the next larger size. In all cases, the MOCP for the
power exhaust should be 15 amps per NEC.
UNIT
549B
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM
(each)
IFM ELECTRIC HEAT* POWER SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE
Min Max RLA LRA FLA FLA kW† FLA MCA MOCP FLA LRA
090
(7
1
/
2
Tons)
208/230-3-60 187 254 12.4 88.0 1.4 10.6
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0
46.1/ 46.1
73.2/ 77.4
87.7/ 94.2
110.6/120.7
129.4/142.4
156.5/173.6
50/ 50**
80/ 80
90/100
125/125
150/150
175/175
49/ 49
74/ 78
88/ 94
109/118
126/138
159/167
271/271
293/296
305/310††
323/331††
338/348††
360/373††
460-3-60 414 508 6.4 44.0 0.7 4.8
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
22.8
43.7
47.5
64.5
72.4
85.5
25**
45**
50**
70
80
90
24
44
47
63
70
82
136
152
155
169
175
186††
102
(8
1
/
2
Tons)
208/230-3-60 187 254 13.9 105 1.4 10.6
49.2/ 49.2 50/ 50** 53/ 53 305/305
7.8/10.4 21.7/ 25.0 76.3/ 80.4 80/ 90 78/ 81 327/330
12.0/16.0 33.3/ 38.5 90.8/ 97.3 100/100 91/ 97 339/344††
18.6/24.8 51.6/ 59.7 113.7/123.8 125/125 112/121 357/365††
24.0/32.0 66.6/ 77.0 132.4/145.4 150/150 129/141 372/382††
31.8/42.4 88.3/102.0 159.6/176.7 175/200 154/170 394/407††
460-3-60 414 508 7.9 55.0 0.7 4.8
25.9 30** 27 158
13.9 16.7 46.7 50** 47 174
16.5 19.8 50.6 60** 50 177
27.8 33.4 67.6 70 66 191
33.0 39.7 75.5 80 73 197
41.7 50.2 88.6 90 85 208††
120
(10 Tons)
208/230-3-60 187 254 19.3 123.0 1.4 15.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3
66.0/ 66.0
93.2/ 97.3
107.7/114.2
149.3/162.3
176.4/193.5
196.5/186.3
70/ 70
100/100
110/125
150/175
200/200
200/200
70/ 70
95/ 99
109/115
147/159
172/188
190/209
365/365
387/390††
398/403††
431/442††
453/467††
469/485††
460-3-60 414 508 10.0 62.0 0.7 7.4
16.5
27.8
33.0
41.7
50.0
19.8
33.4
39.7
50.2
60.1
33.5
58.2
75.2
83.1
96.2
93.6
35**
60**
80
90
100
100
36
58
74
81
93
105
183
203
217
223††
234††
243††
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor-Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor-Fan Motor
RLA Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
POWER EXHAUST
PART NO.
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
MOCP
(for separate
power source)
CRPWREXH021A01 N/A 0.68 N/A 15
CRPWREXH022A01 3.4 N/A 1.32 15
CRPWREXH023A01 N/A 1.4 N/A 15
CRPWREXH028A01 1.7 N/A 0.68 15
CRPWREXH029A01 N/A 0.7 N/A 15
CRPWREXH030A01 1.6 N/A 0.64 15
7
457
549B, 549C