Bryant 549C Heat Pump User Manual


 
52
PERFORMANCE DATA — 548F (cont)
ELECTRIC HEATING CAPACITIES — 548F036-072
*Two heater packages required to provide kW indicated.
†Use CRSINGLE004A00 for units with convenience outlet.
**Use CRSINGLE002A00 for units with convenience outlet.
††Use CRSINGLE002A00 for units with high-static motor and convenience outlet.
NOTES:
1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)
2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW new = 16 kW (215/240)
2
kW new = 12.8 kW (rating at 215 v)
UNIT
548F
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY HEATER
PART NUMBER
CRHEATER - - - A00
SINGLE POINT BOX
PACKAGE NO.
CRSINGLE---A00
036
208/230/240
(single phase)
3.3/ 4.0/ 4.4
4.9/ 6.0/ 6.5
6.5/ 8.0/ 8.7
7.9/ 9.6/10.5
9.8/12.0/13.0*
001
002
003
004
002 & 002
—†
004
004
005
208/230/240
(3 phase)
3.3/ 4.0/ 4.4
4.9/ 6.0/ 6.5
6.5/ 8.0/ 8.7
7.9/ 9.6/10.5
12.0/14.7/16.0
001
002
003
004
005
002
460/480
(3 phase)
5.5/ 6.0
8.1/ 8.8
10.6/11.5
12.9/14.0
006
007
008
009
048
208/230/240
(single phase)
3.3/ 4.0/ 4.4
6.5/ 8.0/ 8.7
9.8/12.0/13.0*
13.1/16.0/17.4*
15.8/19.3/21.0*
001
003
002 & 002
003 & 003
004 & 004
—†
004
005
005
005
208/230/240
(3 phase)
4.9/ 6.0/ 6.5
6.5/ 8.0/ 8.7
12.0/14.7/16.0
15.8/19.3/21.0*
002
003
005
004 & 004
002
003
460/480
(3 phase)
5.5/ 6.0
10.6/11.5
12.9/14.0
21.1/23.0*
006
008
009
008 & 008
060
208/230/240
(single phase)
4.9/ 6.0/ 6.5
6.5/ 8.0/ 8.7
9.8/12.0/13.0*
13.1/16.0/17.4*
15.8/19.3/21.0*
002
003
002 & 002
003 & 003
004 & 004
004
004
005
005
005
208/230/240
(3 phase)
4.9/ 6.0/ 6.5
7.9/ 9.6/10.5
12.0/14.7/16.0
15.8/19.3/21.0*
19.9/24.3/26.5*
002
004
005
004 & 004
004 & 005
—**
002
003
003
460/480
(3 phase)
5.5/ 6.0
10.6/11.5
12.9/14.0
21.1/23.0*
23.4/25.5*
006
008
009
008 & 008
008 & 009
072
208/230/240
(3 phase)
4.9/ 6.0/ 6.5
7.9/ 9.6/10.5
12.0/14.7/16.0
15.8/19.3/21.0*
19.9/24.3/26.5*
002
004
005
004 & 004
004 & 006
—††
002
002
003
003
460/480
(3 phase)
5.5/ 6.0
10.6/11.5
12.9/14.0
21.1/23.0*
23.4/25.5*
006
008
009
008 & 008
008 & 009
548F