149
PERFORMANCE DATA — 542J (cont)
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
LEGEND
*Standard drive range is 817 to 1038 rpm. Alternate drive range is 1082
to 1303. Other rpms may require a field-supplied drive.
NOTES:
1. Maximum continuous bhp is 5.90 and maximum continuous watts
are 5180. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
2. Fan performance is identical for horizontal discharge applications
using horizontal adapter curb (CRRFCURB013A00).
3. See this page for General Fan Performance notes.
GENERAL NOTES FOR FAN PERFORMANCE TABLES
1. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. For additional information on motor performance,
refer to Indoor-Fan Motor Performance table on page 150.
2. Values include losses for filters, unit casing, and wet coils. See
page 151 for accessory/FIOP static pressure information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
542J180 (15 TONS)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
RpmWattsBhpRpmWattsBhpRpmWattsBhpRpmWattsBhpRpmWattsBhp
4500 584 717 0.8 695 952 1.1 798 1205 1.3 893 1483 1.7 984 1786 2.0
4800 609 839 0.9 717 1085 1.2 815 1346 1.5 907 1630 1.8 994 1938 2.2
5100 634 971 1.1 738 1229 1.4 833 1500 1.7 921 1791 2.0 1006 2104 2.4
5400 660 1118 1.3 760 1389 1.6 852 1669 1.9 937 1968 2.2 1019 2286 2.6
5700 687 1284 1.4 783 1566 1.8 873 1858 2.1 956 2165 2.4 1034 2490 2.8
6000 712 1458 1.6 805 1752 2.0 892 2055 2.3 973 2371 2.7 1049 2703 3.0
6300 736 1644 1.8 826 1952 2.2 911 2265 2.5 990 2591 2.9 1064 2930 3.3
6600 763 1856 2.1 851 2176 2.4 933 2502 2.8 1010 2837 3.2 1082 3186 3.6
6900 788 2078 2.3 873 2410 2.7 954 2747 3.1 1029 3093 3.5 1099 3451 3.9
7200 813 2316 2.6 896 2662 3.0 975 3011 3.4 1048 3367 3.8 1117 3734 4.2
7500 841 2584 2.9 921 2943 3.3 998 3304 3.7 1070 3672 4.1 1137 4049 4.5
542J180 (15 TONS)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp
4500 1070 2113 2.4 1151 2458 2.8 1229 2819 3.2 1302 3194 3.6 — — —
4800 1078 2269 2.5 1157 2620 2.9 1233 2990 3.3 1306 3374 3.8 — — —
5100 1086 2439 2.7 1164 2795 3.1 1238 3170 3.5 — — — — — —
5400 1097 2626 2.9 1172 2986 3.3 1245 3366 3.8 — — — — — —
5700 1110 2835 3.2 1183 3200 3.6 1253 3584 4.0 — — — — — —
6000 1122 3053 3.4 1193 3422 3.8 1262 3810 4.3 — — — — — —
6300 1135 3286 3.7 1204 3660 4.1 1271 4052 4.5 — — — — — —
6600 1151 3549 4.0 1218 3928 4.4 1283 4325 4.8 — — — — — —
6900 1167 3821 4.3 1232 4207 4.7 1295 4608 5.2 — — — — — —
7200 1183 4113 4.6 1246 4505 5.0 — — — — — — — — —
7500 1202 4437 5.0 1264 4837 5.4 — — — — — — — — —
Bhp — Brake Horsepower Input to Fan
Watts — Input Watts to Motor
542J