118
PERFORMANCE DATA — 549B, 549C (cont)
ELECTRIC HEATING CAPACITIES — 549B036-120 AND 549C024-060 (cont)
*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW
new
= Heater kW
rated x
(unit power distribution voltage/rated heater voltage)
2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW
new
= 16 kW (215/240)
2
kW
new
= 12.8 kW (rating at 215 v)
MULTIPLICATION FACTORS
NOTE: The following equation converts kW of heat energy to Btuh:
kW x 3.413 = Btuh.
EXAMPLE: 34 kW (at 230 v) heater on 208 v
= 34.0 (.751 mult factor)
= 25.5 kW capacity at 208 v.
OUTDOOR SOUND POWER (TOTAL UNIT)
UNIT
549B
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY
HEATER
PART NUMBER
CRHEATER---A00
ACCESSORY SINGLE
POINT BOX PART NO.
CRSINGLE---A00
090
(7
1
/
2
Tons)
208/230/240
(3 phase)
7.8/ 9.6/10.4 117 007
12.0/14.7/16.0 110 007
18.6/22.8/24.8 111 009
24.0/29.4/32.0 112 009
31.8/39.0/42.4* 112,117 013
460/480
(3 phase)
12.8/13.9 116 006
15.2/16.5 113 006
25.6/27.8 114 008
30.4/33.0 115 008
38.4/41.7* 114,116 —
102
(8
1
/
2
Tons)
208/230/240
(3 phase)
7.8/ 9.6/10.4 117 012
12.0/14.7/16.0 110 012
18.6/22.8/24.8 111 015
24.0/29.4/32.0 112 015
31.8/39.0/42.4* 112,117 017
460/480
(3 phase)
12.8/13.9 116 011
15.2/16.5 113 011
25.6/27.8 114 014
30.4/33.0 115 014
38.4/41.7* 114,116 016
120
(10 Tons)
208/230/240
(3 phase)
7.8/ 9.6/10.4 117 012
12.0/14.7/16.0 110 012
24.0/29.4/32.0 112 015
31.8/39.0/42.4* 112,117 017
37.6/46.2/50.0* 112,110 017
460/480
(3 phase)
15.2/16.5 113 011
25.6/27.8 114 014
30.4/33.0 115 014
38.4/41.7* 114,116 016
46.0/50.0* 115,113 016
HEATER RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 380 440 460 480 550 575 600
240 0.694 0.751 0.918 1.000 — — — — — — —
480 — — — — 0.626 0.840 0.918 1.000 — — —
600 — — — — — — — — 0.840 0.918 1.000
549B,
549C
ARI
RATING
(decibels)
OCTAVE BANDS; Lw (A)
63 125 250 500 1000 2000 4000 8000
024,036,048 76 50.8 63.4 62.2 65.9 69.2 65.9 63.0 56.5
060,072 80 57.6 70.2 66.9 71.7 74.7 72.2 67.8 62.4
090 82 62.3 69.3 71.5 74.7 76.2 72.9 68.7 61.5
102 84 64.6 71.1 73.3 76.9 77.6 73.7 70.6 63.7
120 84 64.6 71.1 73.3 76.9 77.6 73.7 70.6 63.7
ARI — Air Conditioning and Refrigeration Institute
Lw (A)— Unit A — Weighted Sound Power Level
549B, 549C