ELECTRICAL DATA — 549B (cont)
549B036-120 STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)
LEGEND
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If
power distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.
†Heaters are field installed only.
**Fuse or HACR circuit breaker.
††Electrical disconnect cannot be used if electric heater is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percentage of voltage
imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.
POWER EXHAUST ELECTRICAL DATA
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 549B060 unit with MCA = 35.6 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 35.6 amps + 1.6 amps = 37.2 amps
If the new MCA does not exceed the published MOCP, then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If “MCA New” is larger than the published
MOCP, raise the MOCP to the next larger size. In all cases, the MOCP for the
power exhaust should be 15 amps per NEC.
UNIT
549B
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM
(each)
IFM ELECTRIC HEAT* POWER SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE
Min Max RLA LRA FLA FLA kW† FLA MCA MOCP FLA LRA
090
(7
1
/
2
Tons)
208/230-3-60 187 254 12.4 88.0 1.4 7.5
—
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
—
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0
38.2/ 38.2
65.3/ 69.5
79.8/ 86.3
102.7/112.8
121.5/134.5
148.6/165.7
40/ 40**
70/ 70**
80/ 90
110/125
125/150
150/175
40/ 40
65/ 69
79/ 85
100/109
117/129
142/158
242/242
264/267
275/281††
294/302††
309/319††
330/344††
460-3-60 414 508 6.4 44.0 0.7 3.4
—
13.9
16.5
27.8
33.0
41.7
—
16.7
19.8
33.4
39.7
50.2
19.2
40.1
44.0
61.0
68.8
82.0
20**
45**
45**
70
70
90
20
39
43
59
66
78
121
138
141
155
161
171
102
(8
1
/
2
Tons)
208/230-3-60 187 254 13.9 105 1.4 7.5
— — 41.3/ 41.3 45/ 45** 43/43 276/276
7.8/10.4 21.7/ 25.0 68.4/ 72.5 70/ 80** 68/72 298/301
12.0/16.0 33.3/ 38.5 82.9/ 89.4 90/ 90 82/88 309/315††
18.6/24.8 51.6/ 59.7 105.8/115.9 110/125 103/112 328/336††
24.0/32.0 66.6/ 77.0 124.5/137.5 125/150 120/132 343/353††
31.8/42.4 88.3/102.0 151.7/168.8 175/175 145/161 364/378††
460-3-60 414 508 7.9 55.0 0.7 3.4
— — 22.3 25** 23 143
13.9 16.7 43.2 45** 43 160
16.5 19.8 47.0 50** 46 163
27.8 33.4 64.0 70 62 177
33.0 39.7 71.9 80 69 183
41.7 50.2 85.0 90 81 193
120
(10 Tons)
208/230-3-60 187 254 19.3 123.0 1.4 10.6
—
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
—
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3
56.8/ 56.8
84.0/ 88.1
98.5/105.0
140.1/153.1
167.2/184.3
187.3/177.1
60/ 60**
90/ 90
100/110
150/175
175/200
200/200
60/ 60
85/ 89
98/104
136/148
161/177
180/198
337/337
358/362††
370/375††
403/414††
425/439††
441/457††
460-3-60 414 508 10.0 62.0 0.7 4.8
—
16.5
27.8
33.0
41.7
50.0
—
19.8
33.4
39.7
50.2
60.1
28.7
53.5
70.5
78.3
91.5
88.8
30**
60**
80
80
100
100
30
53
69
76
88
99
170
189
203
209
220††
230††
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM — Indoor-Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor-Fan Motor
RLA — Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
POWER EXHAUST
PART NO.
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
MOCP
(for separate
power source)
CRPWREXH021A01 N/A 0.68 N/A 15
CRPWREXH022A01 3.4 N/A 1.32 15
CRPWREXH023A01 N/A 1.4 N/A 15
CRPWREXH028A01 1.7 N/A 0.68 15
CRPWREXH029A01 N/A 0.7 N/A 15
CRPWREXH030A01 1.6 N/A 0.64 15
7
457
549B, 549C