Bryant 549C Heat Pump User Manual


 
5
MODEL NUMBER NOMENCLATURE — 542J150,180 UNITS
ARI* CAPACITY RATINGS
548F036-060
548F072-120
LEGEND
*Air Conditioning and Refrigeration Institute.
†Applies only to units with capacity of 60,000 Btuh or less.
**The IPLV applies only to 2-stage cooling heat pump units.
NOTES:
1. Rated in accordance with ARI Standards 210/240-95 and 270-95.
2. Ratings are net values, reflecting the effects of circulating fan heat.
3. ALL the 548F036-060 units are in compliance with ASHRAE 90.1
2001 Energy Standard for minimum SEER and EER requirements.
Refer to state and local codes or visit the following website:
http://solstice.crest.org/efficiency/bcap
to determine if compliance
with this standard pertains to a given geographical area of the United
States.
4. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature
and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and
80 F db outdoor entering-air temperature.
High-Temp Heating Standard: 70 F db indoor entering-air temperature
and 47 F db, 43 F wb outdoor entering-air temperature.
Low-Temp Heating Standard: 70 F db indoor entering-air temperature
and 17 F db, 15 F wb outdoor entering-air temperature.
UNIT
548F
NOMINAL
TONS
COOLING
HEATING
(High Temp)
SOUND
RATING
(decibels)
Net Capacity
(Btuh)
SEER†
Capacity
(Btuh)
HSPF
Belt
Drive
Direct
Drive
036 3 35,600 10.20 10.00 34,400 6.7 84
048 4 46,500 10.00 9.70 46,500 7.0 80
060 5 57,000 10.00 9.90 57,000 7.5 82
UNIT
548F
NOMINAL
TONS
COOLING
HEATING
(High)
HEATING
(Low)
IPLV**
SOUND
RATING
(decibels)
Net Capacity
(Btuh)
EER
Capacity
(Btuh)
COP
Capacity
(Btuh)
COP
072 6 70,000 9.05 72,400 3.20 42,000 2.14 82
090 7
1
/
2
86,000 9.00 78,000 3.00 39,000 1.80 9.3 86
120 10 112,000 9.00 105,000 3.10 59,000 2.00 9.0 84
COP Coefficient of Performance
db dry bulb
EER Energy Efficiency Ratio
HSPF Heating Seasonal Performance Factor
IPLV Integrated Part-Load Values
SEER Seasonal Energy Efficiency Ratio
wb wet bulb
Nominal Cooling Capacity
150 12 Tons
180 15 Tons
Factory-Installed Outdoor
Air Upgrade Options
C– Economizer
H– 25% Manual Damper
542J E X 150 000 AB H B
542J High-Efficiency Rooftop Units
Electric Heat Pumps
Voltage Designation
E–460-3-60
P–
T–
208/230-3-60
575-3-60
Heat Type
X– No Heat Installed
Electric Heaters
000 No Factory-Installed Electric Heaters
Accessory Field-Installed Electric Heaters
Available
Fan Drive Position
(Standard Motor)
B– Standard Low-Medium
Fan Drive Static Capability
D– Alternate High Fan
Drive Static Capability
Design Series Code
AB Economizer Design Change
Quality Assurance
Certified to ISO 9001:2000
a50-8040