Page 38
(c) Open gas shutoff valve. Restart the
appliance. The ignition sequence will
start again and the burner will start. The
appliance will return to its previous mode
of operation.
Caution
Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a
normal manner, CLOSE MAIN SHUTOFF VALVE.
Do not shut off switch. Contact your heating
contractor, gas company, or factory representative.
Gas Type Air Orifice Gas Orifice
Differential Differential
Natural 4.0 to 4.5" W.C. 4.0 to 4.5" W.C.
(1.0 to 1.1kPa) (1.0 to 1.1kPa)
Propane 4.5 to 5.0" W.C. 4.5 to 5.0" W.C.
(1.1 to 1.2kPa) (1.1 to 1.2kPa)
Note: Long runs of vent or combustion air piping may
reduce the air and gas differential pressures. This
is acceptable, as long as the air and gas pressure
differentials are within 0.1" (0.025kPa) w.c. of each other.
Table 7. Air and Gas Orifice Differentials at Full Fire.
6.3 Shutting Down the Brute Magnum
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain the Brute
Magnum and be sure to also protect building
piping from freezing.
This step to be performed by a qualified
service person.
6.4 To Restart the Brute Magnum
If drained, follow Section 6.1 in this manual
for proper filling and purging.
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest
setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch,
manual reset high limit, etc).
7. Set the temperature controller to the desired
temperature setting and switch on electrical
power.
8. Burner will go through a prepurge period and
ignitor warm-up period, followed by ignition.
Section 7
MAINTENANCE
WARNING
Disconnect all power to the appliance before
attempting any service to the appliance. Contact
with electricity can result in severe injury or death.
7.1 System Maintenance
1. Lubricate the system water-circulating pump, if
required, per the instructions on the pump.
2. If a strainer is employed in a pressure reducing
valve or the piping, clean it every six months.
3. Inspect the venting system for obstruction or
leakage at least once a year. Periodically clean
the screens in the vent terminal and combustion
air terminal (when used).
4. Keep the appliance area clear and free from
combustible materials, gasoline, and other
flammable vapors and liquids.
5. If the appliance is not going to be used for
extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water.
6. Low water cutoffs, if installed, should be
checked every 6 months. Float type low water
cutoffs should be flushed periodically.
7. Inspect and clean the condensate collection and
disposal system yearly.
8. When a means is provided to neutralize
condensate, ensure that the condensate is being
neutralized properly.
9. Inspect flue passages, and clean with brushes/
vacuums, if necessary. Sooting in flue passages
indicates improper combustion. Determine the
cause and correct.
10. Inspect the vent system and air intake system,
and ensure that all joints are sealed properly. If
joints need to be resealed, completely remove
existing sealing material, and clean with alcohol.
Apply new sealing material, and re-assemble.
7.2 Appliance Maintenance and
Component Description
Only genuine Bradford White replacement parts
should be used.
Caution
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
See Figures 27, 28 and 32 for location of gas
train and control components.