Beckett CG25 Burner User Manual


 
5
CG15, CG25, CG50 Burner Manual
Pre-installation Checklist
Indoor Installation
Combustion Air Supply
The burner requires combustion air and ventilation air
for reliable operation. Assure that the building and/or
combustion air openings comply with the latest edition of
the National Fuel Gas Code ANSI Z223.1 (NFPA 54).
For appliance/burner units in con ned spaces, the room
must have an air opening near the top of the room, plus
one near the oor, each with a free area at least one
square inch per 1000 Btu/hr input for all fuel-burning
equipment in the room.
For Canadian installations, refer to latest edition of
CAN1- B149.1 standard.
If there is risk of the space being under negative
pressure, or of exhaust fans or other devices depleting
available air for combustion and ventilation, the
appliance/burner should be installed in an isolated room
provided with outside combustion air.
Clearances
With the burner installed in the appliance, there must
be adequate space in front of and on the sides of the
burner to allow access and operation. Verify that the
clearance dimensions comply with local codes and with
the appliance manufacturer’s recommendations.
Fuel Gas Supply
Verify that the gas supply piping complies with all
applicable local codes and the latest edition of the
National Fuel Gas Code ANSI Z223.1 (NFPA 54).
Insure that the supply gas pipe size is capable of
providing at least the minimum pressure required to the
burner gas train inlet at the burner’s full capacity rating.
Refer to Table 1.
Flue Vent System
The ue gas vent system must be in good condition
and must comply with National Fuel Gas Code ANSI
Z223.1 (NFPA 54) and all other applicable codes having
jurisdiction for vent construction, capacity, and sizing.
Professional Installer’s Responsibility
Section: Pre-installation Checklist
Follow these instructions
exactly
Failure to follow these instructions could
lead to equipment malfunction and result
in asphyxiation, explosion or re.
Please read all instructions before proceeding.
Follow all instructions completely.
This equipment must be installed, adjusted, and
started by a quali ed service agency that is licensed
and experienced with all applicable codes and
ordinances and responsible for the installation and
commissioning of the equipment.
The installation must comply with all local codes and
ordinances having jurisdiction and the latest edition
of the National Fuel Gas Code ANSI Z223.1 (NFPA
54) and CAN1-B149.1 in Canada.
y
y
y
Concealed damage – If you
discover damage to the burner or
controls during unpacking, notify the carrier at once and
le the appropriate claim forms.
High altitude installations – Accepted industry practice
requires no derate of burner capacity up to 2000 feet
above sea level. For altitudes higher than 2000 feet,
derate the burner capacity 2% for each 1000 feet above
the 2000 feet.
50 Hz motors – The burner ratings, air settings and other
adjustments are based on 60 Hz motors at 3450 rpm.
Derate ring capacity 20% when using 50 Hz motors.
Consult factory for speci c application data.
Protect against Dust and
Moisture
Wet or dusty environments could lead to blocked air
passages, corrosion damage to components, impaired
combustion performance and result in asphyxiation,
explosion or re.
This burner is designed for clean, dry installations.
Electrical controls are not protected against rain or
sprayed liquids.
Keep the installation clear of dust, dirt, corrosive
vapors, and moisture.
Protective covers and more frequent maintenance
may be required.
y
y
y
y