Beckett CG25 Burner User Manual


 
10
Mount the burner to the appliance. The burner speci ed
for packaged equipment will have a ange welded for the
required insertion. Follow the appliance manufacturer’s
instructions for mounting.
In the absence of instructions, or for retro ts, make sure
that the air tube insertion dimension, measured along
the side of the air tube from the welded ange to the end
of burner air tube, is correct.
Figure 6 - Custom Mounting Plate
If this dimension cannot be achieved, protect the
end of the air tube by installing a suitable ceramic
refractory material such as a refractory mill board
capable of withstanding at least 2300 degrees F.
The entry hole diameter in the appliance should
be 1” larger than the air tube to facilitate ease of
installation and provide adequate protection.
Referring to Figure 6, if the front plate opening (C)
in the boiler is larger than the burner ange bolt
circle, then a custom mounting plate (A) of at least
1/4” thickness must be used with a suitable high-
temperature refractory material anchored on the re-
side. A suitable high-temperature gasket (B) must be
used for an effective seal.
Attach the plate and gasket to the boiler and tighten
the mounting nuts or bolts securely.
Verify that the air tube is ¼” back from ush (see
Figure 2), and there is nothing blocking the ame
zone that could cause ame impingement.
Mount the Burner
Protect the Air Tube from
Overheating
Overheating could cause damage to the air tube and
other combustion components leading to equipment
malfunction and impaired combustion performance.
The end of the air tube must not extend into the
combustion chamber unprotected unless it has
been factory-tested and speci ed by the appliance
manufacturer.
The end of the air tube should be set back ¼”
from ush with the refractory inside wall to prevent
damage from overheating.
Refer to the instructions outlined in this section for
methods of additional protection.
y
y
y
A
B
C
Key:
A = Burner mounting ange
B = Gasket
C = Appliance mounting plate
Connect Gas Piping
Do Not Use Te on Tape on
Gas Piping
Damage to gas valve cutoff seals and valve bodies could
cause gas leaks and result in asphyxiation, explosion or
re.
Pieces of tape can be cut loose during installation
and lodge in gas valves causing cutoff seal
problems.
Te on tape ‘lubricates’ pipe threads, allowing iron
pipes to penetrate too deeply into aluminum valve
bodies causing distortion and leakage.
Use only pipe sealant compounds that are resistant
to the gas being used.
y
y
y
All gas piping installation must
comply with the latest edition of the
National Fuel Gas Code ANSI Z223.1 (NFPA 54) and
other applicable local codes.
The gas supply system must be sized to deliver at
least the minimum required pressure to the gas train
inlet. Contact your local gas utility for veri cation of
gas pressures, allowable pressure drops, and any local
piping code requirements. Refer to Figure 7 for an
illustration of a gas piping layout and refer to Table 2 for
pipe sizing.
Section: Mount the Burner & Connect Gas Piping