Beckett CG25 Burner User Manual


 
13
CG15, CG25, CG50 Burner Manual
Figure 8A - UL Gas Train - High/Low and Low Fire Start
Figure 8B - UL Gas Train - Modulating
ABBREV.
HGPS
LGPS
MSC
MLTC
MV
SSOV1
SSOV2
TC
TP
U
2PRSSOV
ITEM DESCRIPTION
HIGH GAS PRESSURE SWITCH
LOW GAS PRESSURE SWITCH
MAIN SHUTOFF COCK
MAIN LEAK TEST COCK
MODULATION VALVE
SAFETY SHUTOFF VALVE #1
SAFETY SHUTOFF VALVE #2
TEST COCK
TEST PORT
UNION
HIGH/LOW PRESSURE REGULATING SAFETY SHUTOFF VALVE
When pressure reducing safety
shutoff valves are used, the
distance from the nal shutoff valve (2PRSSOV in
Figure 8A) to the burner manifold must be kept to a
minimum for good light-off reliability. R. W. Beckett
recommends the following maximum lengths:
Pipe Size
1”
1-1/4”
1-1/2”
2”
Maximum Length
12”
15”
18”
24”
If Normally Open Vent Valve (not shown) is used,
the distance between the SSOVs must be kept to a
minimum using the shortest practical nipples.
Section: Connect Gas Piping
LGPS
TC
TC
HGPS
MSC
SSOV1
2PRSSOV MLTC
U
TP
U
SK9982
SK9983
LGPS TC
TC
HGPS
MSC
PRV
SSOV1
SSOV2
MLTC
U
TP
U
MV
SK9984
SK9985