York BP 090 Heat Pump User Manual


 
66307-YIM-B-0606
Unitary Products Group 9
LOCATION
Use the following guidelines to select a suitable location for
these units:
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit
on either north or east side of building.
3. Suitable for mounting on roof curb.
4. For ground level installation, use a level concrete slab
with a minimum thickness of 4 inches (102 mm). The
length and width should be at least 6 inches (152 mm)
greater than the unit base rails. Do not tie slab to the
building foundation.
5. Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed
on a solid, level roof curb or appropriate angle iron
frame.
6. Maintain level tolerance to 1/2” (13 mm) across the entire
width and length of unit.
FIGURE 4 - PREDATOR
®
COMPONENT LOCATION
Tool-less door
latch
Side entry
power and control
wiring knockouts
Simplicity™ Control
board w/screw con-
nector for T-stat wir-
ing and network
connection.
Disconnect location
(optional disconnect switch)
Filter access (2” throw-away)
Roof curbs in eight- and fourteen-inch
heights. Roof curbs for transitioning from
York Sunline™ footprint to the BP Series
footprint are also available.
(field-installed accessory)
Slide-out drain pan
with steel 3/4” FPT
connection
Compressor #1 access (high-
efficiency compressor)
Belt-drive
blower motor
Filter drier (solid
core)
Condenser
section
Slideout motor
& blower
assembly for
easy access
adjustment &
service
Base rails w/fork-
lift slots (3 sides)
and lifting holes)
Compressor #2
access (high-
efficiency com-
pressor)
Terminal block for
hi-voltage connection
Second model name-
plate inside hinged
access panel
TABLE 1: UNIT TEMPERATURE LIMITATIONS
Temperature Min. Max.
Wet Bulb Temp °F (°C) of Air on Evap Coil 57 (14) 72 (22)
Dry Bulb Temp °F (°C) of Air on Cond Coil 0 (-18) 125 (52)
TABLE 2: UNIT VOLTAGE LIMITATIONS
Power Rating
*
*.
Utilization range “A” in accordance with ARI Standard
110.
Minimum Maximum
380/415-3-50 342 456